en – Original instructions
36
P05 Operating time
months
Total months of connection to the electric mains, to add to P06.
P06 Operating time hours
h
Total hours of connection to the electric mains, to add to P05.
P07 Motor Time Months
This parameter shows the total operating time months, to be added
to P08.
P08 Motor time hours
h
This parameter shows the total operating time hours, to be added to P07.
P09 1st error
This parameter stores the last error occurred in chronological order.
The information displayed switches through the values:
•
(Exx): xx indicates the error code
•
(Hyy): yy is the value of hours referred to P05-P06 when the
error Exx happened
•
(Dww): ww is the value of days referred to P05-P06 when the
error Exx happened
•
(Uzz): zz is the value of weeks referred to P05-P06 when the
error Exx happened
Example of visualisation:
E04
→
K10
→
d03
→
U15
P10 2nd error
Saves the penultimate error in chronological occurred.
Other characteristics: like P09.
P11 3rd error
Saves the third from the last error in chronological occurred.
Other characteristics: like P09.
P12 4th error
Saves the fourth from the last error in chronological occurred.
Other characteristics: like P09.
P13 Power Module
Temperature
°C
Temperature of the power module.
P14 Inverter Current
A
This parameter shows the actual current supplied by the frequency
converter.
P15 Inverter Voltage
V
This parameter shows the actual estimated input voltage of the
frequency converter.
P16 Motor Speed
rpmx10
This parameter shows the actual motor rotational speed.
P17 Software version
This parameter shows the Control Board software version.
6.5.2 Settings Parameters
No. Parameter
Description
P20 Password
entering [0÷999]
The user can enter here the system password, which gives access to all system parameters:
this value is compared with the one stored in P22.
When a correct password is entered, the system remains unlocked for 10 minutes.
P21 Jog mode
[MIN÷MAX
]
It deactivates the internal controller of the unit and forces the actual Control Mode (ACT):
the motor starts and the value of P21 becomes the temporary ACT setpoint. It can be
changed by just entering a new value on P21 without confirming it; otherwise, it causes
immediate exit from temporary control.
P22 System
password
[1÷999]
This is the system password, and must be the same as the password entered in P20.
Default: 66.
P23 Lock Function
[OFF, ON]
By using this function, the user can lock or unlock parameter setting in the main menu.
When ON, enter the P20 password to change the parameters.
Default: ON.
*
Depending on the type of pump used