Motor Lead Lengths – 3-Phase Motors –
Based on Service Factor Amps, 30º C Ambient and 5% Voltage Drop
Motor Rating
60º C and 75º C Insulation - AWG Copper Wire Size
Volts
HP
kW
FLA
SFA 14
12 10 8 6 4 3 2 1 1/0
2/0
3/0
4/0
.5
.37
3.8
2.9
657
1045
1667
2641
4109
.75
.55
3.8
4.5
423
674
1074
1702
2648
1 .75 4.6 5.5 346 551 879 1392 2166 3454 4342
200
1.5 1.1 6.3 7.2 265 421 672 1064 1655 2638 3317
2 1.5 7.5 8.8 217 344 549 870 1354 2158 2714 3427 4317 5449
3 2.2 10.9 12.0 159 253 403 638 993 1583 1990 2513 3166 3996
5 3.7 18.3 20.2 94 150 239 379 590 940 1182 1493 1881
2374 2995 3781
4764
7.5 5.5 27.0 30.0 64 101 161 255 397 633 796 1005 1266
1598 2017 2546
3207
.5 .37 2.4 2.9 756 1202 1917 3037 4725 7532 9469
.75 .55 3.3 3.9 562 894 1426 2258 3513 5601 7041 8892
1 .75 4 4.7 466 742 1183 1874 2915 4648 5843 7379
230
1.5 1.1 5.2 6.1 359 571 912 1444 2246 3581 4502 5685 7162 9040
2 1.5 6.5 7.6 288 459 732 1159 1803 2874 3613 4563 5748 7256 9155
3 2.2 9.2 10.1 217 345 551 872 1357 2163 2719 3434 4326 5460 6889 8696 10956
5 3.7 15.7 17.5
318 503 783 1248 1569 1982 2496 3151 3976 5019 6323
7.5 5.5 24 26.4
334 519 827 1040 1314 1655 2089 2635 3327 4192
.5
.37
1.3
1.5
2922
4648
7414
.75
.55
1.7
2.0
2191
3486
5560
8806
1
.75
2.2
2.5
1753
2789
4448
7045
1.5
1.1
2.8
3.2
1370
2179
3475
5504
460
2
1.5
3.3
3.8
1153
1835
2926
4635
7212
3
2.2
4.8
5.3
827
1315
2098
3323
5171
5 3.7 7.6 8.5 516 820 1308 2072 3224 5140
7.5 5.5 12.2 13.5 325 516 824 1305 2030 3236 4068 5138 6472
10
7.5
1.5
1.1
2.0
2.4
2283
3631
5792
2
1.5
2.7
3.3
1660
2641
4212
6671
575
3
2.2
3.7
4.1
1336
2126
3390
5370
5
3.7
7.0
7.6
721
1147
1829
2897
4507
7.5
5.5
9.1
10.0
548
871
1390
2202
3426
THREE PHASE, 4" MOTOR WIRE CHART
THREE PHASE 4" MOTOR WIRE CHART