Country
Electrical Data
Switzerland
6 A, 250 V, AC
Sweden
10 A, 230 V, AC Resistive load
3A, 250 V, AC Inductive load
5 A, 30 V, DC Resistive load
*1 mA, 5 V, DC, Gold Contact
* Part no: 594 79 19 & 594 79 20
Safety data for EX approved installation
Maximum input voltage, U
i
:
30 V
Maximum input current, I
i
:
100 mA
Maximum input power, P
i
:
1.2 W
Depth of immersion:
Max 20 m
For cable length 20 m:
Maximum internal capacitance, C
i
:
1.8 nF
Maximum internal inductance, L
I
:
10 μH
Approvals
CE, CSA, SEMKO, NEMKO, DEMKO, EX
LVD approval according to EN61058
CSA approval: Cert no. 1330172
Cl.I Zone 0, Gr. IIC;
CL.I Div.1 Gr A, B, C&D
Cl.II Gr. E, F&G
Cl.III when installed to the certified Intrinsically Safe relay, Ex ia, rated for the locations per
submitter control drawing and installation manual.
Ex approval:
IECEx ia IIC T4 Ga: -20°C<Ta<60°C
IECEx NEMKO 09.008
ATEX II 1G ia IIC T4
NEMKO 10ATEX 1082
The applied standards are:
EN 60079-0:2009/IEC 60079-0:2007
EN 60079-11:2007/IEC 60079-0:2006
EN 60079-26:2007/IEC 60079-26:2006
Intrinsically safe circuits are required for the automatic control system. - Use a EX-safety
barrier (e.g. Prod. no. 84 01 07).
0080
R
Safety
Flygt ENM 10 Level regulator Installation, Operation and Maintenace Manual
7
Summary of Contents for Flygt ENM 10
Page 1: ...Flygt ENM 10 Level regulator Installation Operation and Maintenace Manual...
Page 2: ......
Page 18: ......
Page 19: ......