Xylem Bell&Gosset Hoffman Speciality SCC Series Instruction Manual Download Page 4

4

PUTTING THE UNIT INTO SER

VICE

1.

Assure that the unit is piped in accordance with instructions
in this manual.

2. Isolate tank before performing any system leak test. Do not

pressurize the tank as part of the leak test. Failure to do this
can result in serious injury or death.

3. Check floats and alternators for free operation.

4. Wire unit per National Electrical Code. See representative

wiring diagrams.

5. Install drain plugs.

6. Fill receiver half full of water to prime pump(s) and prevent

possible damage to pump seals. Avoid freezing conditions
after unit receiver has been filled.

7. Check for proper rotation of all three phase motors.

Rotation must be clockwise looking down on the motor as
indicated by directional arrow on pump casting. If pump
runs backwards, interchange two wires (3 phase only).

8. Throttle plug cock in discharge line until pressure at pump

(while pump is discharging) approaches pump rated pres-
sure. Tighten plug nut to secure adjustment.

9. Remove start-up label (below) from panel (if applicable)

after complying with instructions.

10. If possible, observe operation thru several cycles.

W

ARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

W

ARNING: HIGH VOLTAGE

Disconnect and lock out power befor

e connecting or

servicing unit. Failure to follow these instructions could
result in serious injury or death.

CAUTION:

DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.

Inspect pump seal r

egularly for leaks. Replace as required.

Failure to follow these instructions could result in injury or
property damage.

CAUTION: 

DO NOT REVERSE

Reverse operation can cause extensive damage to

pumps. Jog the motor to test for direction of rotation. Failure
to follow these instructions could result in injury or property
damage.

OPERA

TION AND MAINTENANCE

Operators must be familiar with all sections of this manual to

understand the operation of the unit.

Hot water, steam and electricity can be hazardous.

Check motor nameplate for any lubrication requirements.
Pumps require no lubrication.

NOTICE / AUTO REST

ART

Single phase motors will r

estart automatically after thermal

overload protector trips.

Overload thermal relays in starters must be reset manually.

A properly installed unit should function unattended for long
periods of time. Periodic checks to assure proper operations
are highly recommended. Refer to trouble shooting section
when necessary.

A variety of control options are available and are furnished in
accordance with user specifications. Refer to wiring diagrams
(when furnished) to determine control switch settings.

The inlet strainer (when furnished) is intended to protect the
pump and system. Periodic cleaning should be included in the
maintenance schedule. Check frequently in new systems.

W

ARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

W

ARNING: HIGH VOLTAGE

Disconnect and lock out power befor

e connecting or

servicing unit. Failure to follow these instructions could
result in serious injury or death.

CAUTION: 

SUBSEQUENT DAMAGE

A unit showing symptoms of possible pr

oblems

(overflow, noise, leaks, vibrations, continual operation, etc.)
must be corrected immediately. Failure to follow these
instructions may result in full liability for subsequent injury or
property damage.

SAFETY INSTRUCTIONS
SEE COVER OF THIS MANUAL

ELECTRICIAN/INST

ALLER/OPERATOR

REMOVE AND DESTROY THIS T

AG AFTER —

1. ASSURING THAT ALL PUMPS ROTATE CLOCKWISE PER ARROWS CAST ON VOLUTES. (JOG

PUMP MOMENTARILY TO TEST – INTERCHANGE ANY TWO MOTOR POWER WIRES TO
REVERSE 3PH MOTORS.)

2. ASSURING THAT SHIPPING LOCKS HAVE BEEN REMOVED FROM ALL FLOAT SWITCHES.

Summary of Contents for Bell&Gosset Hoffman Speciality SCC Series

Page 1: ...INSTRUCTION MANUAL DN0156 REVISION H Hoffman Specialty Vented Condensate Units Watchman Series WC WCS and Series SCC WCS Simplex Watchman WCS8 20B SCC4 WC Duplex Watchman WCD 12 20BMA...

Page 2: ......

Page 3: ...D BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE DASHED LINE WIRING COMPONENTS BY OTHERS MODEL SCC2 SCC3 SCC4 DUPLEX 3 PHASE UNITS WITH CONTROL PANEL CONNECTION DIAGRAM ELEMENTARY DIAGRAM LINE 1 H3 H 4...

Page 4: ...tructions could result in injury or property damage OPERATION AND MAINTENANCE Operators must be familiar with all sections of this manual to understand the operation of the unit Hot water steam and el...

Page 5: ...es to rise or fall with one pump in operation the lever will continue to travel to a further position at which point the second switch will be operated throwing the stand by pump across the line MOUNT...

Page 6: ...aces of the seal clean of any foreign matter Moisten the carbon section of the rotating part of the seal and place onto the shaft to seat against ceramic Place seal spring onto shaft 13 Hold motor sha...

Page 7: ...ring Ring 1 DP1665 7 Capscrew 4 DJ0083 8 Wear Ring 1 DP0482 9 Pipe Plug 1 4 1 P39040 10 Water Slinger 1 DP0848 Seal Kit including Mechanical Seal Head Gasket Case to 1 180013 Receiver Gasket Complete...

Page 8: ...h the motor vertical top end bell down and with belleville washers or finger springs properly oriented in the top end bell recess lower the rotor and head assembly as a unit holding it by rotor shaft...

Page 9: ...Ring 1 DP1602 16 Head to Case Capscrews 3 DJ0077 17 Case to Receiver Gasket 1 DG0060 Seal Kit including Mechanical Seal Head Gasket Case to 1 180013 Receiver Gasket Complete Pump and Motor Assembly 1...

Page 10: ...loose If it is hold in place with grease Using clean lint free cloth wipe mating surfaces perfectly clean Soap shaft and push seal onto shaft so that carbon will contact ceramic seal If spacer is requ...

Page 11: ...1 DP1603 5 Wearing Ring 1 DP0482 8 Impeller Capscrew 1 DJ0213 9 Impeller Washer 1 DJ0267 10 Capscrews 8 DJ0066 16 Water Slinger 1 DP0848 Seal Kit including Mechanical 6 7 Seal Head Gasket 1 180014 Cas...

Page 12: ...200 N Austin Avenue Morton Grove Illinois 60053 Phone 847 966 3700 Fax 847 965 8379 www xylem com bellgossett Bell Gossett is a trademark of Xylem Inc or one of its subsidiaries 2019 Xylem Inc DN0156H...

Reviews: