Figure 8
Pumps with motors 256 NEMA frame and below can be
installed with the shaft horizontal and the piping vertical
with supports for the piping (not shown) adequate to
carry the loads from the pump and piping. See
on page 15
Figure 9
Pumps with motors 256 NEMA frame and below can also
be installed with the shaft horizontal and the piping
horizontal with supports for the piping (not shown)
adequate to carry the loads from the pump. See
on page 15
Figure 10
e-80 pumps have a four bolt circle on the bottom of the
volute to accept an ANSI/ASME flange that can be used
with a connected pipe as a temporary pump support
while the permanent pump piping or pump supports are
being fitted to the pump. This support can only be used
to handle the pump weight as it is not suitable to resist
loads in other directions. See
For installations in grooved piping systems when the pump is supported by the piping,
flange locking type grooved piping connections are required to prevent the pump from
rotating in the piping.
4 Installation
Series e-80 INSTRUCTION MANUAL
15
Summary of Contents for Bell & Gossett e-80 Series
Page 1: ...INSTRUCTION MANUAL P2002877 Rev C Series e 80 ...