Xylem BCF Instruction Manual Download Page 9

START

16

11

8

3

13

10

5

2

15

12

7

4

14

9

6

1

8. All bolted joints should be tightened uniformly and in a

diametrically staggered pattern as illustrated below:

9. Frequently and at regular intervals, observe interior and

exterior condition should be according to scale build-up.

CAUTION:

Neglect in keeping all tubes clean may result

in complete stoppage of flow through some tubes with
consequent overheating of these tubes, resulting in severe
expansion strains, leaking tube joints, and damage to the heat
exchanger.

FRONT HEAD

FRONT HEAD GASKET

CORE

(BUNDLE & SHELL ASSEMBLY)

REAR HEAD

REAR HEAD GASKET

MOUNTING LEGS

RENEWABLE ANODES 

(ZINC)

10.Exchangers subject to fouling or scaling should be cleaned

periodically. A light sludge or scale coating on the tube
greatly reduces its effectiveness. Therefore, low-fouling
fluids should be used in the shell side of all heat
exchangers with non-removable tube bundles. A marked
increase in pressure drop and/or reduction in performance
usually indicates cleaning is necessary, especially if the
unit has been checked for air or vapor binding and this has
been found not to be the cause. Since the difficulty of
cleaning increases rapidly as the scale thickens or deposits
increase, the interval between cleanings should not be
excessive. interior and exterior condition should be
according to scale build-up.

ANODES

1. Some exchangers may be equipped with renewable

anodes. The purpose of the anodes is to inhibit electrolytic
corrosion. In order to remain active the anodes must be
kept free of scale or other surfaces coatings.

2. On some applications where electrolytic corrosion is not a

problem, pipe plugs may be substituted for the anode. The
pipe plug material selected should be softer than the base
part to avoid pipe thread damage.

BCF HCF & SSCF Heat Exchangers Installation, Operation, and Maintenance Manual 

8

Summary of Contents for BCF

Page 1: ...Models BCF HCF SSCF Fixed Tube Sheet Heat Exchangers INSTALLER PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE INSTRUCTION MANUAL...

Page 2: ...ety 3 General safety rules 3 Safety equipment 4 Product Warranty 4 Product Description 5 General description 5 Installation 6 Installation 6 Operation 6 Startup 6 Maintenance 7 Maintenance and cleanin...

Page 3: ...ot covered in this manual could cause death serious injury or damage to the equipment This includes any modification to the equipment or use of parts not provided by Xylem If there is a question regar...

Page 4: ...l 3 Hazard categories can either fall under hazard levels or let specific symbols replace the ordinary hazard level symbols These are examples of other categories that can occur They fall under the or...

Page 5: ...local sales and service representative within the warranty period The product is used only under the conditions that are described in this manual All service and repair work that is done by Xylem aut...

Page 6: ...RAL DESCRIPTION BCF HCF SSCF heat exchangers are fixed tube heat exchangers using 1 4 3 8 and 5 8 diameter tubes BCF units use copper tubes brass shells and CI bonnets SSCF units are made of all 316 S...

Page 7: ...edium through the shell and the cooling medium through the tubes When the hot fluid is dirty or fouling it is better to put it through the tubes because they are easier to clean With single pass units...

Page 8: ...her excessively corroded nor insulated with scale Scrape to a bright surface 4 Inspect filters in the system to prevent foreign matter from entering the exchanger WARNING Proper precautions must be ta...

Page 9: ...e used in the shell side of all heat exchangers with non removable tube bundles A marked increase in pressure drop and or reduction in performance usually indicates cleaning is necessary especially if...

Page 10: ...Standard Xchange is a trademark of Xylem Inc or one of its subsidiaries 2018 Xylem Inc BCF HCF SSCF September 2018 Xylem www xylem com standardxchange...

Reviews: