Baud Rate and Parity
The baud rate and parity is set simultaneously using a single register write command (function code 0x06) of address 0x0001. The
upper byte defines the parity, and the lower byte defines the baud rate from a list of standards.
Parity
None
0x00
Odd
0x01
Even
0x02
Baud Rate
9600
0x00
19200
0x01
38400
0x02
57600
0x03
115200
0x04
Request
Function Code
1 byte
0x06
Register Address
2 bytes
0x0001
Register Value
2 bytes
0x0200
Request
Function Code
1 byte
0x03
Register Address
2 bytes
0x0001
Register Value
2 bytes
0x0001
Response
Function Code
1 byte
0x06
Register Address
2 bytes
0x0001
Register Value
2 bytes
0x0200
Response
Function Code
1 byte
0x03
Register Address
2 bytes
0x0002
Register Value
2 bytes
0x0200
Error
Error Code
1 byte
0x86
Exception Code
1 bytes
0x03 (Illegal Data Value)
The serial configuration can also be read using a read holding registers command (function code 0x03) of address 0x0000.
Modbus Configuration & Commands