Version 001 (25.8.2020) 

Page 

1

 of 

2

 

D-502-0172 

The Quick Manual will guide you through a quick installation of the product, but in no case could it replace the full operating manual. A 
complete operating manual is available on our website 

www.xvent.cz 

or can be downloaded using a QR code. 

 

Xvent s.r.o.

                           

Poděbradská 289 

                            

53009 Pardubice-

Trnová

                               

[email protected] 

-

 

The air curtain 

is designed for indoor covered and dry areas with an ambient temperature from +5 ° C to +40 ° C

-

 

The air curtain can also be used for environments with higher non-condensing humidity corresponding to the degree of protection IP54 
and IP44, according to EN 60529 depending on the type of air curtain. However, a maximum of 80%. The air curtain can also be used in a 
corrosive environment C2, according to EN ISO 9223. The air curtain must not be operated in an environment with a risk of explosion and 
increased dust. 

-

 

Neither the manufacturer nor the supplier is liable for damage caused by incorrect use of the air curtain. The risk is borne by the user. 

-

 

The air curtain must not be operated during finishing construction activities, especially during activities in which excessive dust is 
generated, eg: grinding of concrete, plasterboard, etc ... 

Use of the Wind air curtain

 

Technical parameters

 

Vertical installation

 

-

 

The air curtain must stand on a flat, cohesive and firm surface. 

-

 

The correct height of the air curtain must be at least 100 mm longer than the 
height of the opening. If the height of the opening is higher or equal to the air 
curtain height, you must attach another air curtain. 

-

 

Use the "WIND-HOLDER" base (accessory) to fasten the air curtain to the floor. 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                                                         

 

 

 

 

 

 

QUICK MANUAL FOR USE AND INSTALLATION 

 

Use a smart device (mobile phone, tablet, etc.) equipped with this technology to read the QR code. 

 

Installation and connection of the air curtain may only be 
carried out by a trained person with the appropriate 
authorization for the connection of electrical equipment, 
who has the appropriate tools at his disposal. During 
installation, all instructions and recommendations given in 
the Operation and Installation Manual for the WIND must be 
observed. 

Before starting any installation or maintenance work, it is 
necessary to turn off the power and secure the switch 
before turning it on again. When handling the air curtain, 
take its weight into account and observe safety. 

Anchoring the base 
(anchors, dowel screws 
must be diameter 10 
mm. A washer must be 
placed under the head 
of the anchoring screw, 
nuts, for better weight 
distribution of the air 
curtain. The air curtain 

can be rotated ± 20 ° in 

the base. 

-

 

The Wind air curtain is designed to separate the indoor and outdoor environment with a 
stream of air. This function prevents the escape of indoor air from the indoor environment to 

the outdoor environment with open doors, gates, etc.… Another function of t

he air curtain 

with closed doors, gates is the possibility to heat the interior by hot air heating. When 
purchasing additional accessories - filter, the air curtain is also used to filter the air of the 
indoor environment. 

-

 

The air curtain is intended primarily for entrances to industrial halls, warehouses, sports 
facilities, workshops, smaller establishments, and also to the entrances of commercial 
premises. 

Installation 

 general information

 

The air curtain must be positioned in the way, that the edge of exhaust of air curtain will be in direction 
to the wall aligned towards the door frame of the screened opening. The minimum distance between 
the side of the air curtain and the wall, the ceiling is 0.1 m and between the fan intake and the wall, the 
ceiling is 0.3 m (from flammable substances 0.5 m). The air curtain - the exhaust must always be turned 
at lea

st 10 ° outwards from the opening. Otherwise, proper operation 

of the air curtain cannot be 

guaranteed. Local installation conditions must be taken into account. 