background image

 

Verze 002 (21.1.2020) 

Stránka 

1

 z 

2

 

D-502-0166 

 

The Quick Manual will guide you through a quick installation of the product, but in no 

case could it replace the full operating manual. A complete operating manual is 
available on our website 

www.xvent.cz

 and available for download using a QR code. 

 

Xvent s.r.o.

                           

Poděbradská 289                             

53009 Pardubice-Trnová                               

[email protected] 

Regulator power supply 

terminals 

1~230VAC 

50/60Hz 

 

Max. regulator current 
capacity: 

230 VAC / 5A 

Recommended cross-
section of conductors: 

1.5mm

2

 

Terminal for exchanger fixture servo 

control 

The contact only interrupts/controls 

the phase conductor, which is connected to 
the supply phase of regulator. The neutral 

conductor is connected directly from the 
power supply. 

Maximum current capacity: 

230 VAC / 5A (resistive load)

 

Clamp for regulator control by 

means of magnetic potential-free 
contact 

- logic of NC (opening) 

contact switching. 

 

Contact load capacity: 

12VDC / 10 mA 

Recommended cross-section of 
conductors: 

from 0.5 mm

to 1.5 mm

2.

 

Control voltage terminals from 
the EC 

fan 0–10VDC (+); GND (-). 

Regulator control range 2-
10VDC. 
Contact load capacity: max 2mA 

Recommended cross-section of 
conductors: from 0.5 mm2 to 1.5

 

2.      

Technical parameters

 

- Input voltage                1~230VAC 50/60Hz        - Current                                  5A 
- Temperature adjustment range     5–35°C        - Dimensions    85 x 85 x 30mm 
- Protection class                                 IP20             - Weight                            0.16Kg 

E  

 

 

 

 

 

 

 

 

Description of the regulator 

 

The regulator is used to continuously control the speed of the EC fan. The fan speed may also be controlled by an integrated room 

thermostat, depending on the temperature of the area. The fan speed control and thermostat control is implemented as continuous 
adjustment on the front panel of the regulator. For information on the operation of the connected equipment, a signal diode is located 
between the (turning) control elements. Furthermore, the regulator is equipped with a 1~230VAC phase contact 1~230VAC and a 12VDC low-
potential contact. The regulator is designed for wall installation. The maximum recommended distance of the regulator from the controlled 
EC-motor is 100 m at conductor cross-section of 1 mm

2

. Longer or shorter distances are possible depending on the selected conductor cross-

section and the resulting real voltage loss calculation.  

 

Description of controls and connecting terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                     

                                                                                                    

1.

 

Umístění Regulátoru 

QUICK MANUAL FOR USE AND INSTALLATION

 

Use the smart device (mobile phone, tablet, etc.) 
equipped with this technology to read the QR code.

 

Room thermostat 

– allows 

the adjustment of the 
required temperature in the 
range of 5 to 35°C. Based on 
the difference between the 
ambient temperature and the 
required temperature, the 
connected equipment is 
switched off or on. It is also it 
possible to deactivate the 
room thermostat by switching 
to the "OFF” end position. 

Indicator diode 

– indicates operation of the entire regulator. 

If the diode is lit, the regulator is on. If the regulator is not lit, 
the regulator is switched off.

 

Continuous fan speed regulator – 

allows continuous fan speed 

adjustment in any position from 

minimum to maximum speed as 
required by the user. The "OFF" 

position allows the entire 

regulator to be switched off.  

The "OFF" position does not 
ensure isolation of the 
controlled equipment from the 
supply voltage; isolation needs 
to be ensured separately on 
the supply side. 

E - MARK I 

The regulator may only be installed 
and connected by a trained person 
with the appropriate authorization to 
connect electrical equipment and with 
suitable tools and means.

 

Reviews: