Description of regulator

 

-

 

The regulator is used to continuously control the speed of the EC-motors with the control input 0-10VDC 
without connection to the mains power supply. 

 

-

 

The motor speed is controlled continuously by the control element (a knob) on the front panel of the 
regulator. 

 

-

 

For information on the operation of the connected equipment, the operating signal diode is located in 
the upper part of the front panel. 

 

-

 

The regulator is supplied with direct voltage of 10 VDC from the EC-motor. T

 

-

 

he regulator is designed for wall installation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.1.

 

Description of connecting terminals

 

-

 

Spring terminals with manual locking are used to connect the wires. A strand-type conductor (cable) 

and a solid conductor (wire) in the cross-section range from 0.5 to 1.5 mm² can be installed in the 

terminals.  

-

 

Before inserting the wire into the terminals, first press the locking orange button. Then slip in the wire, 

release the lock and slightly pull it out of the terminal to verify that the wire is properly secured. If the 

wire needs to be removed from the terminal, the procedure is the same.  

-

 

The optimum cross-section of the conductor must be selected according to the actual length of the 

conductor route; however, the cross-section of the conductor may be 1.5 mm

2

.  

-

 

All wires shall be connected to terminals with adequate force to prevent damage to them or damage to 
the electrical board. Stripping of cables to individual conductors should be 10mm. In the case of strand-
type conductors, an end piece must be pressed on (tube).

 

 

 

 

Signalling diode 

– signals the operation of the entire 

regulator. If the diode is lit, the regulator is active. If 
the regulator is not on, it is switched off.

 

Continuous fan speed regulator 

– allows smooth fan 

speed  setting  in  any  position  from  minimum  to 
maximum  fan  speed  as  required  by  the  user.  The 
"OFF"  position  allows  the  entire  regulator  to  be 
switched  off.  The  "OFF"  position  does  not  provide 
disconnection of the controlled equipment from the 
supply voltage – it must be performed separately on 
the supply

 

Summary of Contents for ELEMENTAIR B-MARK I

Page 1: ...1 Verze 1 GBR 11 3 2020 D 502 0168 OPERATION AND INSTALLATION INSTRUCTIONS...

Page 2: ...gulator 3 3 Regulator installation 4 3 1 Regulator location 4 3 2 Installation 4 3 3 Installation in the working position 5 3 4 Electrical installation and electrical connection 5 4 Technical paramete...

Page 3: ...ght to change this manual without prior notice 1 2 Control of delivery and storage Before starting the installation and before unpacking the regulator from the box it is necessary to check for any tra...

Page 4: ...ng 3 2 Installation The regulator can be mounted on a wall o In an under plaster electrical junction box hereinafter referred to as the boxes with the central opening for the supply cable The supply c...

Page 5: ...ocal regulations are respected 3 4 Electrical installation and electrical connection The regulator may be connected only by persons qualified to handle electrical devices up to 1000V The regulator mou...

Page 6: ...the wire release the lock and slightly pull it out of the terminal to verify that the wire is properly secured If the wire needs to be removed from the terminal the procedure is the same The optimum...

Page 7: ...the cross section according to the length of the conductor route EC fan connection terminals Description terminals for connecting the control voltage from the EC fan PWM 0 10VDC GND with resistance 1...

Page 8: ...ng to legal regulations The warranty only applies if all installation and maintenance instructions are followed The warranty covers manufacturing defects defects in material or defects in the operatio...

Page 9: ...he company s service centre The complaining party shall receive a written statement on the result of the complaint warranty repairs In the event of an unjustified complaint all costs associated with t...

Reviews: