Xtreme Power Conversion Corporation
Web/SNMP Cards
Page 44
UPS Management
Troubleshooting
Troubleshooting UPS Connection
The SNMP/Web adapter front panel features a LED marked „UPS‟. This LED should be OFF in normal condi-
tions. If the LED is ON then there is a problem in the communication with the UPS.
NOTE
: It may take up to one minute for the adapter to synchronise the communication with the UPS.
Also, the SNMP/Web adapter will signal a Communication Lost alarm if communication with the UPS is lost and
cannot be re-established.
Troubleshooting Local Connection
For troubleshooting problems in local (serial) console connection to the adapter refer to the following table.
Problem
Recommended resolution
Port already in use – e.g. Windows
HyperTerminal reports the following
problem:
Close all applications and services that are currently using the port
selected for the connection to the device.
Attempt a new connection.
Cannot connect to the adapter
Check the serial cable (a straight 1:1 serial cable is required) and its
connection. Check the settings of the terminal application:
115,200bps, 8 data bits, 1 stop bit,
parity none, flow control none
Cannot login to the local console
Verify username and password used. Verify that the user has been
correctly defined and configured by the administrator.
Cannot use interactive menus
Check the settings of the terminal application:
Terminal emulation VT-100