Xtreme Power Conversion Corporation
M90 User’s Manual
Page 73
Uninterruptible Power Supply
M90-140 Specifications
MODEL NUMBER
M90-20k140 M90-40k140
M90-60k140 M90-80k140
M90-100k140 M90-120k140 M90-140k140
CAPACITY
Power rating
20kVA/18kW
40kVA/36kW
60kVA/54kW
80kVA/72kW
100kVA/90kW 120kVA/108kW 140kVA/126kW
Power modules
Up to 140kVA N+1 (8 x 20kVA)
Battery modules
4, 8, 12, 16, 20, 24, 28 or 32 internal battery modules
INPUT
Voltage nominal
208/120V
Frequency nominal
50/60Hz auto-sensing
Voltage range
121–253VAC*
(L-L)
Frequency range
40–70Hz
OUTPUT
Voltage
208/120V
Frequency
50/60Hz ± 0.5Hz
THD (full load)
< 2%
Efficiency
Up to 94% online mode, or 98% ECO mode
Overload capacity
105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for 200ms
BATTERY
Nominal voltage
± 120V
SYSTEM
Charge Current
(programable)
8A
16A
24A
32A
40A
48A
56A
DIMENSIONS
&
UPS Enclosure
23.6"W x 43.3"D x 79.1"H / 657 lbs
WEIGHT
Battery Enclosure
23.6”W x 43.3”D x 79.1”H / TBD lbs
Power module
19.0”W x 28.0”D x 5.1”H / 74 lbs
Battery module
4.1”W x 28.3”D x 6.0”H / 68 lbs
ENVIRON
-
MENT
Temperature
0–40°C (32–104°F)**
Altitude
5,200 ft above sea level**
Audible noise
< 65dBA at 1m
APPROVALS
UL-1778 (TUV), cUL, FCC A, RoHS, Energy Star (all pending)
WARRANTY
2 years (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)
INCLUDED IN BOX
User manual, RS-232 cable, Ramp for unloading UPS enclosure, ViewPower Software
AVAILABLE OPTIONS
External maintenance bypass, 480V input transformer, output distribution,
battery temperature sensor
*Depending on load level **Battery life is reduced above 30°C, UPS capacity derates above 30°C and 5,200 ft above sea level