XPRT-6kVA, XPRT-10kVA USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation
Page 44
FIG 47 – 10KVA BYPASS CIRCUIT BREAKER
4.
Close all switches and breakers upstream from the UPS.
5.
Switch the INPUT CIRCUIT BREAKER placed on the rear side of the UPS to “ON” position (FIG 48).
The GREEN “UTILITY INPUT” LED will be illuminated.
FIG 48 – 10KVA INPUT CIRCUIT BREAKER
6.
Wait 45 seconds to allow the output voltage to stabilize.
7.
Press the keypad “UPS ON” for 1 second. Within a few seconds “OPERATION” LED will be
illuminated and “BYPASS” LED will be extinguished.
8.
Close the OUTPUT CIRCUIT BREKAER on the rear side of the UPS (FIG 49).
FIG 49 – 10KVA OUTPUT CIRCUIT BREAKER
9.
The UPS is now in operation; equipment connected to the UPS output can now be switched on.
10.
Load % will be shown on the “LOAD” LED BAR.