![Xtreme Power Conversion P90-ISO10MB User & Installation Manual Download Page 47](http://html1.mh-extra.com/html/xtreme-power-conversion/p90-iso10mb/p90-iso10mb_user-and-installation-manual_891027047.webp)
Xtreme Power Conversion Corporation
P90L 6kVA & 10kVA User’s Manual
Page 47
Uninterruptible Power Supply
Installation as a Rack Unit
Terminal Block Explanations for Input, Output
Terminal Block Explanation
L1–N1:
Utility Input / UPS Input (use same terminals as Utility Input)
G1:
Input Ground
L2–N2:
Connect to UPS Output Terminal
G2:
Connect to UPS Output Ground Terminal
L11–L12–N11–L22–N22:
the Output Terminals of the Unit
G3:
The Output Ground Terminals of the Unit
Output Wiring Explanation
• The maximum output current for each terminal is 30A (6K) or 50A (10K).
• If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output voltage shall be 240Vac/120Vac
UPS Input shares
Utility Input terminal