NXRi-6KL, NXRi-10KL USER MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion® (XPC) Corporation (Rev 2/7/13)
Page 45
Operating mode/status
Battery mode
Description
When the input voltage is beyond the acceptable range or power failure,
UPS will use backup power from battery and alarm will beep every 4
seconds.
LCD display
Bypass mode
Description
When input voltage is within acceptable range and bypass is enabled, turn
off the UPS and it will enter Bypass mode. Alarm beeps every two
minutes.
LCD display
Battery Test
Description
When UPS is in AC mode or CVCF mode, press “Test” key for more than
0.5s. Then the UPS will beep once and start “Battery Test”. The line
between I/P and inverter icons will blink to remind users. This operation is
used to check the battery status.
LCD display
Fault status
Description
When UPS has fault happened, it will display fault messages in LCD panel.
LCD display