background image

October 2, 

2012 

XTRALIS VESDA LASER INDUSTRIAL (VLI) – QUICK SETUP TECHNICAL GUIDE 

 

For internal use only                                                 Authored by: Manuel Espaillat 

 

 

 

  

Design Review 

The design of VLI pipe networks in ASPIRE2 should have taken the following recommendations into consideration: 

• 

Utilize at least two pipes in the design (Pipe 2 and Pipe 3 recommended when only using two pipes) with a 

pipe flow rate of at least 25+ ltr/min and a detector flow rate at least 50+ ltr/min as per ASPIRE2 , use higher aspirator 
speed setting if required. 

• 

Ensure that for single pipe installations ASPIRE2 pipe flow rate is at least 50+ ltr/min, use a higher aspirator 

speed setting if required.  

• 

Exhaust pipes (ASPIRE2 calculations are not needed) unless there is substantial pressure differential where 

the exhaust pipe needs to go back to the sampling area, keep the exhaust pipe length at a minimum. 

• 

Connect the VLI to the installed pipe network, select relevant pipes in use through VSC, block pipes not in 

use and ensure that the exhaust is not blocked. 

Installation 

VLI is often applied to harsh/extreme industrial environments, some key things to remember would be: 

• 

Countersink sampling points whenever possible to aide in preventing particulate/contaminant build up 

around pipe sampling holes.  Please refer to the “

Counter-Sinking Holes (VLI) Application Note”

 (doc number 

19782_01). 

 

• 

If the VLI is installed inverted (upside down) to prevent water condensate from reaching or affecting the VLI 

internal components, please refer to the 

“Removal of Water Condensate Application Note” 

under the section 

“Water Condensate Removal – Water Trap”

 (doc number 17405_01). 

 

 

 

AUTHORISED DISTRIBUTOR OF VESDA 

www.flamestop.com.au | [email protected]

Summary of Contents for VESDA VLI

Page 1: ...ia a standard local Type B USB port This type of USB cable is most commonly used with USB printers The connector that plugs into the computer is known as Type A The USB cable is NOT included with the...

Page 2: ...ferential where the exhaust pipe needs to go back to the sampling area keep the exhaust pipe length at a minimum Connect the VLI to the installed pipe network select relevant pipes in use through VSC...

Page 3: ...he list of available detectors then select Next 9 Enter a unique name for the device then select Finish 10 Go to the Connection menu and select Open Connection and view next the Bacnet USB connection...

Page 4: ...monitoring is required use the Detector GPI Ensure that Detector GPI is connected in such a way that voltage 5V appears on its terminals for GPI activation How to clear fault 322 on VLI 880 If fault...

Page 5: ...UIDE For internal use only Authored by Manuel Espaillat 5 Double click again on VESDA VLI on left and select Input outputs you will get following warning Press OK you will get the following screen AUT...

Page 6: ...nternal use only Authored by Manuel Espaillat 6 Change VESDAnet Card GPI to Reset as shown below Press OK double click VEASDA VLI on left again will get following screen and then select Empty under IF...

Page 7: ...SER INDUSTRIAL VLI QUICK SETUP TECHNICAL GUIDE For internal use only Authored by Manuel Espaillat 7 Then press OK then reset detector fault 322 will clear AUTHORISED DISTRIBUTOR OF VESDA www flamestop...

Reviews: