8.2.2
Using a PC
a. From the View menu select Device View.
b. Select the detector to be normalized from the displayed list of devices.
c. From the Device menu, select Normalize Air Flow to start the function.
d. To check the airflow level, select the Current Flow command under Device menu after normalizing.
8.3
VESDAnet Communication Check (For VN Model only)
Note:
This test verifies the VESDAnet system is functioning and all devices connected on VESDAnet are
communicating.
a. List all VESDAnet numbers for all devices connected onto the communication loop.
b. Refer to Section 8.3.1 for LCD programming or Section 8.3.2 for PC programming.
c. Verify the VESDAnet number for each device on the network is shown on the list.
d. If there are some devices not found on the display list, check the VESDAnet cabling to all the devices is
correct.
8.3.1
Using LCD Programmer
a. Go to Show Wiring Order menu and press
↵
.
b. Check the displayed list shows all the connected devices and the VESDAnet number for each device is
correct.
c. Check for any devices not connected and troubleshoot if necessary.
8.3.2
Using a PC
a. Select Device list from the View menu.
b. Check the displayed list shows all the connected devices and the VESDAnet number for each device is
correct.
c. Check for any devices not connected and troubleshoot if necessary.
8.4
Basic Pass/Fail Smoke Test
Note:
This test verifies the detector will sense smoke. It does not replace any appropriate commissioning
test.
a. Isolate the detector by pressing the Reset key for more than 2 seconds.
b. Check the Reset/Isolate LED lights up.
c. Inject smoke into any sampling air hole.
d. Wait for one of the red LEDs on the front panel to light up.
e. If the LED does not light up contact a fully trained accredited VESDA engineer.
f. Reset the detector by pressing the Reset switch once when the smoke test passes.