![Xtralis VESDA VFT-15-C Product Manual Download Page 22](http://html1.mh-extra.com/html/xtralis/vesda-vft-15-c/vesda-vft-15-c_product-manual_3771977022.webp)
VESDA VFT-15 Product Guide
VESDA by Xtralis
16
www.xtralis.com
CN7: Output Relay Interface
1
FIRE 2
C
Requires 7 x 0.2 - 6 A (24 AWG) cable
Notes:
l
Maximum relay contact rating is 2 A @ 30 VDC.
l
Refer to Section 5.4.1 for details of individual sector relay
options.
l
For use in UL/ULC Fire Alarm Application, refer to
Appendix F Item 2.
2
NC
3
NO
4
FIRE 1
C
5
NC
6
NO
7
ACTION
C
8
NC
9
NO
10
ALERT
C
11
NC
12
NO
13
FAULT
C
14
NC
15
NO
Note:
Connection CN14 is only used for special applications.
Connector
Pin Description
Description
8-pin RJ45
Standard Ethernet
connections
Standard Ethernet cable.
Notes:
l
Refer to Section D.4 for further details.
l
Not tested for UL/ULC Fire Alarm connection application.
Table 3-3: Connections to Processor Board
Output Relay Interface (i606)
1
RELAY 1
C
Requires 7 x 0.2 - 6 A (24 AWG) cable
Notes:
l
Maximum relay contact rating is 2 A @ 30 VDC.
l
Refer to Section 5.4.1 for full operational details.
2
NC
3
NO
4
RELAY 2
C
5
NC
6
NO
7
RELAY 3
C
8
NC
9
NO
10
RELAY 4
C
11
NC
12
NO
Table 3-4: Connections from 4 Channel Relay Board (Optional Module)