
VESDA-E VEU-A00 Product Guide
36
www.xtralis.com
Notes:
l
The polarity of the data wires must be maintained throughout the network.
l
In order for the detector to be able to detect ground faults on the VESDAnet wiring, the Ground Reference
Terminal (Figure 4-33) must be connected to the local ground.
A+
A-
B-
Shield
Module 1
Module 2
Module 3
Module 5
Module 4
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
(VESDA-E VEU)
Figure 4-35: Example closed loop VESDAnet network
The VESDA-E VEU-A00 detector is shipped with the VESDAnet A and B terminals looped. Remove the A
and B links prior to connecting the detector to the VESDAnet. If the detector is not to be networked with other
devices, then do not remove the A and B links.
Shield
A-
A+
Shield
B-
B+
Figure 4-36: Closed loop for standalone detectors with VESDAnet capability
Note:
Refer to the VESDA-E Communications Guide for further information.
Summary of Contents for VESDA-E VEU-A00
Page 1: ...VESDA E VEU A00 Product Guide November 2018 Document 22061_12 Part Number 30275 ...
Page 2: ......
Page 10: ...VESDA E VEU A00 Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VEU A00 Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 52: ...VESDA E VEU A00 Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VEU A00 Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEU A00 Product Guide 100 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEU A00 Product Guide 106 www xtralis com Z zone 57 59 77 101 ...