Ducts Application Note 

 

VESDA-E 

35424_02 

 

 

Figure 4: Top view of the inlet tubes positions, including duct mounting 

bracket for a small ventilation duct. 

These sampling points should be located in the middle of the duct width at least 50 mm (2 inches) from the 
side walls. 

 

Note! 

Nominal sampling point spacing is 0.2 m (0.66 ft.). 

 

Sampling Pipe Configuration in Large Ducts 

1.2.1  VESDA-E VEP-1P 

Large ducts are defined as those with widths of 1 to 2 m (3.28 to 6.56 ft). For these ventilation ducts, it is 
recommended that the inlet pipe of the smoke detector be in two branches. The figure below (Figure 5) shows 
a side view of a duct section with the relative insertion points for the inlet and exhaust pipes. The two inlet 
branches are located at a quarter of the height (H) of the duct with the exhaust pipe inserted mid-height 
approximately 0.5 m (1.64 ft) downstream of the inlet pipes. 

 

Figure 5: Side view of the inlet and exhaust  

pipe positions for a large duct. 

The  following figure (Figure  6) shows a cross-section view of the same duct with the positions of the inlet 
branches and exhaust pipe indicated. The number of inlet pipe sampling holes, recommended hole size and 
spacing are presented in Table 2. 

Summary of Contents for VESDA-E VEP-1P

Page 1: ...DUCTS APPLICATION NOTE February 2021 Doc No 35424_02...

Page 2: ...mation contained in this document will assist you when designing VESDA E systems for this type of application Note This system is not suitable for use in flexible ducts Related Products VESDA E VEP 1P...

Page 3: ...1 3 2 VESDA E VEA 5 2 VESDA E System Installation 6 Environmental Conditions 6 2 1 1 VESDA E VEP 1P 6 2 1 2 VESDA E VEA 7 Key Installation Considerations 7 3 VESDA E System Commissioning 8 Hole Orien...

Page 4: ...a quarter of the height of the duct Figure 1 Side view of the inlet and exhaust pipe positions for a small ventilation duct A top view of the above installation is shown below Figure 2 The number of...

Page 5: ...m 0 66 ft 1 1 2 VESDA E VEA Return air sampling is achieved with microbore tubes for VEA system inserted in the return air duct behind the exhaust grill it is recommended the tubes are installed facin...

Page 6: ...commended that the inlet pipe of the smoke detector be in two branches The figure below Figure 5 shows a side view of a duct section with the relative insertion points for the inlet and exhaust pipes...

Page 7: ...le spacing is 0 4 m 1 3 ft The exhaust pipe must have 4 10 mm 13 32 inch sampling holes regardless of the width of the duct These holes should be located in the middle of the duct width at least 50 mm...

Page 8: ...uct is poor it is recommended that all holes on the inlet and exhaust pipes face downstream that is 180 to the incoming airflow The pipes should always be held in position at the duct walls with fitti...

Page 9: ...tside the duct where the detector is to be installed and the temperature of the air inside the sampling pipes of the detector You should measure the temperature and humidity both inside the duct and i...

Page 10: ...ream of humidifiers heating coils and filters Upstream of fresh air intakes For a smoke detector mounted on the duct ensure there are no tangible vibrations when the duct system is in full operation I...

Page 11: ...nd then record the Flow 5 Insert the inlet and exhaust smoke detector pipes in the duct with the holes facing the airflow and record Flow at the smoke detector 6 Slightly rotate the pipes so that the...

Page 12: ...xible tube containing water as shown Figure 9 ensuring all connections are airtight 2 Face the holes on both the inlet and exhaust pipes to the airflow Slightly rotate the pipes so that the water leve...

Page 13: ...tector Cover the electronics during this test with a sheet of paper 5 Introduce smoke inside the detector s interior housing using a smoke can 6 Place the smoke can s nozzle 0 5 m 1 5 ft away from the...

Page 14: ...1 Check flow readings at the smoke detector s Differences in flow readings from those of previous site visits require further investigation such as inspection of the pipes sampling tubes integrity for...

Page 15: ...mendation on system design Xtralis has not assessed the recommendation on system design for compliance with any codes or standards that may apply nor have any tests been conducted to assess the approp...

Reviews: