ICAM by Xtralis
ICAM ILS-2 Product Guide
www.xtralis.com
31
11 Specifications
Table 11-1: General ILS-2 Specifications
Number of Detectors
2, High Sensitivity Analog Addressable
Filtration
Single stage dust particle filter
Flow Monitoring
Thermal device, high and low thresholds. 10 element bar graph indication.
Supply Voltage
20 to 30 VDC (24 VDC Nominal)
Relay Contact Ratings
1 A at 30 VDC
Maximum Supply
Current
350 mA at 24 VDC with no aspirating pipe. See table below for typical
Currents/Fan Speeds.
Maximum Pipe Length
2 x 100 m
Environmental
Protection
IP65 with exhaust fitted (IP23 without)
Operating Temperature
Tested to: -10º to 55ºC
Recommended Detector Ambient : 0º to 38ºC
Sampled Air: -20º to 60ºC
Operating Humidity
10 to 95% RH (non-condensing)
Approvals
EN54-20 by VdS (G206066)
CE Certification
EN 61000-6-3:2007+A1:2011 (EMC Emissions)
EN 50130-4:2011 +A1:2014 (EMC Immunity)
CPR (305/2011/EU), DoP 25999
Table 11-2: Typical Current Consumption vs Fan Speed
Bargraph Value
0
1
2
3
4
5
6
7
8
9
Fan Speed
1
2
3
4
5
6
7
8
9
10
Current (mA)
110
120
130
150
170
190
220
235
265
300
Note:
Typical current consumption figures for different fan speeds. Results are based upon an ILS-2
installation with 10 m of standard, 25 mm aspirating pipe per channel. The unit was powered from a
24 VDC power supply.