Xtralis VESDA LCD Programmer Product Guide
Xtralis
VESDA
®
18
www.xtralis.com
33.
Relay Startup Mode
- Displays the energize/de-energized condition for each relay.
If required, use the
+ -
and
keys to change the energized/de-energized state of
relays.
ADM
34.
Latching
- This screen displays the latched/unlatched relay condition for different
levels of alarms and faults. In the latched condition the reporting of an alarm or a
fault continues to be reported even after the event is over. Manual intervention is
necessary to reset. If the condition is unlatched the reporting of the condition
automatically stops once the event is over. To latch an alarm or a fault place a
against the respective alarm level or fault. The isolate function is fixed for
unlatched and cannot be changed.
ADM
Scrn
No.
Description
Min.
Access
Level
↵
Parameter
Default
Relay Startup Mode
Relay 2 & 3 energized
Energized
Relays 1, 4-7 (4-12)
Energized
Parameter
Default
Latching
Sector (1-4)
N/A
Fire 2
Latched
Fire 1
Latched
Alert
Latched
Scanning N/A
Urgent Fault
Latched
Minor Fault
Latched
Isolate
Unlatched