Xtralis VESDA LCD Programmer Product Guide
Xtralis
VESDA
®
38
www.xtralis.com
122.
Miscellaneous
-
•
Isolate remind - Provides an option to enable or disable the Beeper reminder for
Isolate function
•
Latch Alarms - This provides a YES/NO option to latch/unlatch all Alarms
•
Latch Faults - This provides a YES/NO option to latch/unlatch all Faults
ADM
123.
LCD Programmer
- Select the LCD Programmer and press
.
USR
124.
Status
- Displays the current status for:
•
Current User Level
•
Current Access Level
•
Faults
•
Software Version Installed
•
Configuration Code
USR
125.
Address (Zone) Number
- If the LCD Programmer has been allocated a Address
(Zone) Number, it is displayed in this screen. This is only for VLS.
ADM
126.
Location
- Allocate a VESDA Zone name and location and assign these to the
LCD Programmer.
ADM
127.
Power Supply Number
- Input the number of the power supply that is assigned to
the detector. If the VESDA Intelligent power supply is not being used enter “0”.
ADM
128.
Address Control Lockout
- This screen allows you to lock or unlock the button
functions on any Display in the VESDA Zone. This stops someone logging on at an
OPERATOR level from using the zone control or system control function. The
buttons controlled are:
•
Mode/Test
•
Silence/Scan
•
Reset
•
Isolate
ADM
129.
Factory Defaults
-
•
Factory Defaults - To restore factory defaults, highlight Restore and press
.
•
Defaults OK - Highlighting Start and pressing
will acknowledge Factory
Default settings and clear faults 12, 30, 31, 33, 34, 35, 38, 57, 68 and 72.
DST
ADM
Scrn
No.
Description
Min.
Access
Level
Parameter
Default
Isolate Remind
Enabled
Latch Alarm
Enabled
Latch Fault
Enabled
↵
↵
↵