VESDA-E VEP-A10-P Product Guide
www.xtralis.com
63
5.5.7
Referencing Options
Periodically, smoke and other pollutants from external sources may enter a protected zone temporarily raising
the smoke level. In this case the detector will detect the background smoke and generate an alarm.
Referencing is a system design technique employed to compensate for such rises in background smoke
levels and therefore reduce nuisance alarms in high sensitivity areas.
A separate non-scanning VESDAnet-capable detector is used to draw air from the external source and
produce a reference reading of the background level of smoke and pollutants. The reference reading is then
subtracted from the smoke level of the VEP-A10-P detector monitoring the protected area. This allows the
VEP-A10-P detector to determine if a rise in smoke levels is due to background pollution or a problem inside
the protected area. The ability to compensate for the background level of smoke greatly reduces the chance of
false alarms.
The smoke level from the reference detector which is subtracted from the smoke level of the VEP-A10-P
detector monitoring the protected area is limited to 50% of the Fire 1 alarm threshold of the VEP-A10-P.
A single reference detector can be used by multiple VESDA detectors within the protected area.
The percentage of reference smoke level subtracted can be set differently for each detector monitoring the
protected area. This is set using the dilution factor parameter.
There may be a time delay before the smoke moves from the external source to the protected area. This delay
can be accounted for by delaying the measured reference smoke level before subtracting it from the VEP-A10-
P detector smoke level. This is set using the delay parameter..
Note:
Refer to Section 5.6 on page 68 for the default settings.
Figure 5-17: Referencing Options
The Referencing configuration options are as follows:
l
Referencing Enabled:
If checked, referencing is enabled.
l
Detector:
The name of the detector or system which provides the reference signal. Select from other
non-scanning detectors on the VESDAnet.
l
Delay:
The length of time between the measurement of the external smoke level by the reference
detector and the internal subtraction of this smoke level from the VEP-A10-P smoke level.
l
Dilution Factor:
The percentage of the reference signal to be subtracted from the VEP-A10-P.
Summary of Contents for VESDA-E VEP-A10-P
Page 2: ......
Page 8: ...VESDA E VEP A10 P Product Guide vi www xtralis com This page is intentionally left blank ...
Page 12: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 54: ...VESDA E VEP A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...
Page 78: ...VESDA E VEP A10 P Product Guide 70 www xtralis com This page is intentionally left blank ...
Page 102: ...VESDA E VEP A10 P Product Guide 94 www xtralis com This page is intentionally left blank ...
Page 106: ...VESDA E VEP A10 P Product Guide 98 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VEP A10 P Product Guide 104 www xtralis com Z zone 55 57 73 99 ...