https://www.XPOtool.com
Item 63908–63910
Page 6
The Tool Experts
11 2022-1
F17
Minimum frequency
10
The minimum operating fre-
quency of the water pump
should not be changed.
F18–F24
Occupied
A change is invalid and it is rec-
ommended not to change the
value!
F25
Direction of operation of
the motor
0
“0”: clockwise rotation; “1”:
counter-clockwise rotation. This
setting must be checked in the
event of a shutdown.
F26
Slew rate
10
Change the slew rate of the mo-
tor here (in
Hz
⁄
s
).
F27
Minimum percentage
40
Percentage of operation from
minimum to full speed
F28
Allowing the determination
of lack of water
1
“0”: determine whether there is
a lack of water; “1”: do not deter-
mine whether there is a lack of
water
F29
Limit of 40
% lack of water
95
Limit of lack of water
F30
Limit of 50
% lack of water
155
Limit of lack of water
F31
Limit of 75
% lack of water
420
Limit of lack of water
F32
Limit of 100
% lack of water
720
Limit of lack of water
F33
Class and power
1500
Standard power 1.5
kW.
F34
Fixed end code
23205
The fixed end code cannot be
changed.
Note!
A factory error may differ from what is specified in the specifications, which is a normal phenom-
enon.
Error codes
Error code
Error type
Possible cause
Solution
E0
Control board EEPROM error
EEPROM damage
Have EEPROM re-
placed.
E1
Communication error
Anomaly found in the control
panel and in the board
Contact a specialist.
E2
Pressure sensor error
– Insufficient contact at the
pressure sensor connection
– Damage to the pressure sen-
sor
– Check whether the
connection has become
loose.
– Have pressure sensor
replaced.
E9
Main control panel EEPROM
error
EEPROM damage
Restore factory settings
or contact a specialist.
P0
IPM module overcurrent pro-
tection
UVW phase error
Check whether there is
a short circuit between
three phases of the 3-
phase system.
P1
Power pickup error
Fault in the current measure-
ment circuit
Contact a specialist.