Xpelair Xpelair SL150T Installation And Maintenance Instructions Download Page 2

A

B

C

D

SL100 Overall Dimensions

SL150 Overall Dimensions

Setting the fan.

SL100T / SL100PIR / SL150T / SL150PIR Only.

To adjust the over-run period turn the control (T) clockwise to increase and anti-clockwise to decrease – see Figure F.

SL100HT / SL150HT Only – see figures F and G.

The pre-set humidity operation is factory set at approximately 75% Relative Humidity (RH), but can be adjusted between 65% 
and 85% RH by control H.

The over -run timer can be adjusted up to 30 minutes by control T – see Figure F.

Turn the controls clockwise to increase RH or time and anti-clockwise to decrease – see Figure F.

The fan can be set so that there is a 2-minute time delayed start to its operation when used with an external on/off switch.
To set the time delay start to ON (fan does not start for 2 minutes) set the jumper switch to position shown in figure F.
To set the time delay start to OFF (fans starts immediately) set the jumper switch to position shown in figure F.

Using the fan.

SL100 / SL150 Only

Operate the fan using the on/off switch. Repeat to switch off.

SL100P / SL150P Only

Operate the fan by pulling and releasing the cord. Repeat to switch off.

SL100T / SL150T Only

Operate the fan using an on/off switch (not supplied). When the switch is turned off, the fan continues to operate for the set 
time delay. To adjust the over-run period, turn the control “T” clockwise to increase and anti-clockwise to decrease – see 
Figure F.

SL100HT / SL150HT Only – see Figures F and G.

Automatic mode

- The fan automatically adjusts to slow changes in natural humidity levels without operating the fan.  If the 

humidity levels increase at a rate slower than 5% RH in 5 minutes, up to the pre-set humidity level, the fan will not be triggered 
by humidity. This is to prevent nuisance triggering of the fan. If humidity levels increase quicker than 5% RH in 5 minutes the 
fan will operate. When relative humidity drops the fan continues to operate for the adjustable time delay.

Manual mode

- Use the integral pull cord switch. When the fan is switched off, it goes into automatic mode. Light flashes when 

the fan is operating in manual mode.

External operation

- Use the external on/off switch. When the fan is switched off, the fan continues to operate for the 

adjustable time delay then goes into automatic mode. The fan can be set so that there is a 2-minute time delayed start to its 
operation when used with an external on/off switch.

SL100PIR / SL150PIR Only

The sensor detects movement in the room and activates the fan. When movement is sensed, the fan will run for a pre-set 
overrun period and any further movement sensed will re-start the sequence. This ensures that the room is only ventilated 
after use.

When the fan is first installed there will be a stabilising period of approximately five minutes. During this time the fan will run 
for up to 2 minutes.

All Fans

Re-fit the front cover by hooking in the top corners first, and then swing the cover down to fit the bottom corners. Re-fit the screw.
Re-fit the electrical cover.

Cleaning (recommended once a month).

1.

Before cleaning, isolate the fan completely from the mains supply.

2.

Remove the front cover by removing the screw from the underside of the cover and pulling off the cover from the bottom 
corners first.

3.

To clean the front cover, either wipe it with a damp, lint free cloth or wash it with warm soapy water. Thoroughly dry the front 
cover and refit.

4.

Do not immerse the fan in water or other liquids to clean any other parts of the fan.

5.

Do not use strong detergents, solvents or chemical cleaners

6.

Allow fan to dry thoroughly before use.

7.

Apart from cleaning, no other maintenance is required.

Summary of Contents for Xpelair SL150T

Page 1: ...outside UK see international below United Kingdom Xpelair have a comprehensive range of services including Free technical advice help desk from Engineers on all aspects of ventilation Free design service quotations and site surveys Service and maintenance contracts to suit all requirements Please ask for details By telephone on Techline 44 0 844 372 7766 By fax on Techfax 44 0 844 372 7767 At the ...

Page 2: ...ity This is to prevent nuisance triggering of the fan If humidity levels increase quicker than 5 RH in 5 minutes the fan will operate When relative humidity drops the fan continues to operate for the adjustable time delay Manual mode Use the integral pull cord switch When the fan is switched off it goes into automatic mode Light flashes when the fan is operating in manual mode External operation U...

Page 3: ...ole ƒ100mm for SL100 range or ƒ150mm for SL150 range Preparing the fan for installation Remove the front cover by removing the screw from the underside of the cover and pulling off the cover from the bottom corners first Remove the electrical cover by removing the 2 screws Mount the fan in the hole If working above ground floor level safety precautions must be observed If installing in a wall or c...

Page 4: ...or core drill equipment if available Mortar to make good the hole around the ducting FOR SL100 Range If ceiling mounting the fan You will need the use of appropriate ancillaries for termination These items are available from Xpelair 1 WT10 Termination ducting kit 2 FD100 Flexible Ducting 3 XCT100 Condensation Trap FOR SL150 Range If wall mounting the fan you will also need SLWK15 Wall Kit or alter...

Reviews: