![Xpelair Simply Silent LVCV4SR Installation And Maintenance Instructions Manual Download Page 7](http://html1.mh-extra.com/html/xpelair/simply-silent-lvcv4sr/simply-silent-lvcv4sr_installation-and-maintenance-instructions-manual_3919297007.webp)
For Australia Only –LVCV4SR
These models are permanently connected to the supply and operation is controlled by a remote switch. They should be
directly wired to the supply through an approved 10A wall mounted surface switch with at least 3mm clearance between
contacts.
Preparing the Fan for installation.
1.
Remove the front cover/baffle assembly by depressing the latch on the underside of the cover and pulling off the
front cover / baffle from the bottom (See Figure D).
Mark the position of the back-plate
2.
Hold the back-plate so that the level line marked on it is orientated horizontally.
3.
Carefully insert the fan tube into the wall duct.
4.
Mark on the wall the positions of the fixing holes in the back-plate.
5.
Remove the back plate from the ducting.
6.
Drill screw holes in these positions if necessary, and fit wall plugs and screws as required. The fan may also be fixed
to a wall tube using the clamping brackets. See 10 below.
Mount the back-plate.
7.
Feed the mains cable through the cable entry hole in the back plate to the terminals.
8.
Insert the fan tube of the back-plate into the wall duct/ceiling as before.
9.
Fasten the back-plate to the wall/ceiling using appropriate fasteners. See figure A.
10.
If using screws, do not over tighten. The fan may also be fixed to a wall tube using the clamping brackets. Tighten
the screws until the fan is firmly secured to the tube – see figure C.
Fixing the transformer directly – see figure B
11.
Remove top cover from transformer
12.
Position on the wall and mark the fixing holes
13.
Drill and plug the two holes and fix the transformer
For loft mounting: The transformer can be fixed to a wooden surface
For concealed wiring: Use the knockouts (Y)
Wire the fan electrical connections.
14.
Make sure the mains supply is isolated. Switch off the mains electrical supply and remove fuses.
15.
Feed the cable to the terminal block. Wire the fan as shown in Figure H.
Wiring the transformer.
Always use the cable labyrinth to restrain the cable.
16.
Wire the transformer as shown in figure H. Ensure all connections are tight.
17.
Route the cable through the labyrinth as shown. Ensure the cable is firmly retained.
18.
Fit the cover and retain with the screws.
19.
Make sure the mains supply is isolated, switch off the mains electrical supply and remove fuses.
20.
Connect the cable from the isolating switch to the electrical supply wiring.
21.
For fixed wiring circuits the protective fuse for the appliance must not exceed 5A.
Wet Rooms: On/Off switch must be situated so that it cannot be touched by
persons making use of the bath or shower.
If working above ground floor level, safety precautions must be observed.
If installing in a ceiling, appropriate termination ancillaries are required. Follow
instructions provided.