December 2020 

 08/100245/0           

 

Installing the Ventilation Unit 

The ventilation unit must always be firmly fixed through the four mounting points provided 

Ensure the unit is installed by either of the following methods:  

1.  Using suitable wood screws with a head size 

≥8mm 

2.  Using threaded bolts 

≤5mm with a head size ≥8mm 

 

 

NOTE: 
The ventilation unit is well balanced however, if desired, antivibration 
mounts with 

threaded bolts ≤5mm

 could be used.

 

Connecting the Ducting 

1.  Push the 125mm solid duct on the XEL spigot. 

2.  Push the 125mm to 150mm adapter into the 125mm solid duct. 

3.  (XELH version only) Insert the cold side of the heater into the adapter.   

4.  Place one of the supplied worm drive clips over the flexible duct. 

5.  Fix the flexible ducting to the adapter or heater and tighten the worm drive clip. 

6.  Place the second worm drive clips over the flexible duct. 

7.  Fix the flexible ducting to the 150mm to 200mm adapter. 

8.  (XELH version only) Drill an 8mm hole in the 150mm side of the adapter and 

insert the temperature probe from the heater as shown on the right. 

9.  Push the adapter onto the installed diffuser mounting ring. 

 

 

NOTE: 
When testing the ventilation unit check the ducting for any air leaks and seal with duct tape if necessary.

 

Electrical Connection 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION OR 
MAINTENANCE.

 

All  installations  must  be  supervised  by  a  qualified  electrician.  Installations  and  wiring  must  conform  to  current  IET  Wiring 
Regulations (BS7671) (UK), local or appropriate regulations (other countries). 

A means for disconnection must be incorporated in the fixed wiring in accordance with wiring regulations. 

Check that the electrical rating shown on the fan matches the mains supply. 

This appliance is intended for connection to fixed wiring. The connection should be made with a double insulated cable with cable 
cores greater than 0.75mm

2

; which has been appropriately specified for this specific application by a qualified professional. 

 

WARNING: THIS APPLIANCE MUST BE EARTHED.

 

 

 

Remove  the  cover  by  undoing  the  eight  screws 
identified in the image to the right.  

 

A  long  reach  PZ2  screw driver  at  least  150mm  long  is 
required for this step. 

 

 

Summary of Contents for 110015

Page 1: ...ts reserved Material contained in this publication may not be reproduced in whole or in part without prior permission in writing of Glen Dimplex Glen Dimplex UK LTD trading as Glen Dimplex Heating Ven...

Page 2: ...nit via the G4 filter on the cover The casing incorporates a 125mm spigot for easy connection to the supplied ducting Safety Instructions This ventilation unit is intended exclusively for the ventilat...

Page 3: ...fuser Mounting Ring 8 200mm Supply Air Diffuser 9 Duct Heater Everdri XELH Version Only Position of air supply diffuser It is recommended that the supply air diffuser is installed in a central locatio...

Page 4: ...Care should be taken to ensure ducting is as straight and uncompressed as possible with minimal bends This will reduce resistance in the air flow path allowing greater performance at lower speed setti...

Page 5: ...erature probe from the heater as shown on the right 9 Push the adapter onto the installed diffuser mounting ring NOTE When testing the ventilation unit check the ducting for any air leaks and seal wit...

Page 6: ...Firmly connect the two sides of the plug Fix the cables by either Routing the cable in the labyrinth Fixing with the cable clamp NOTE If using the labyrinth ensure the cable is securely fitted inside...

Page 7: ...Speed 2 Control L Trickle Speed Using a small long handle screw driver adjust the potentiometer as required by turning the knob using the central slot Turn clockwise to increase speed Turn anti clockw...

Page 8: ...8 December 2020 08 100245 0 Alternative Switch Option Connection with a three speed selector switch Connection with sensors or several change over switches...

Page 9: ...oke or CO detector must be normally closed NC and will go open circuit OC in the event of a fire When the ventilation unit detects an open circuit the fan will stop to prevent feeding fresh air to a f...

Page 10: ...the extract of cooking smells or moisture laden air When in use it is advisable to open window vents or a window to allow the moisture laden air to escape The middle position would be the normal runni...

Page 11: ...ours LED on for 2 short flashes 3000 to 4000 hours LED on for 3 short flashes 4000 to 5000 hours LED on for 4 short flashes 5000 to 6000 hours LED on for 5 short flashes 6000 to 7000 hours LED on for...

Page 12: ...f 21856AW Time Delay Unit DT20B Ref 21850AW Air Quality Sensor AQS Ref 92097AW Three Speed Selector Switch Ref 91266AW Three Speed Controller Ref 91457AA Ancillaries Duct Heater Ref 300001022 Raises t...

Page 13: ...for 5 years from date of purchase Xpelair reserve the right to repair or replace the unit Keep your purchase receipt Any problems contact the address below Outside the UK See International section In...

Page 14: ...The ventilation unit has been packaged carefully to protect it from damage during transport The transport packaging consists of recyclable raw materials Please ensure to dispose of it in an environmen...

Reviews: