15. BATTERIES MAINTENANCE NAD REPLACEMENT 

 

15.1.- Battery Care 
 

When battery backup time is noticeable shorter it is time to replace batteries. To get longer lifetime we recommend applying 
a deep discharge every 3 months. Operation temperature should be below 25ºC. When UPS is storage periodic recharge 

must be performed as indicated in below table: 

 

Storage Temperature 

Recharge Frequency 

Recharge Time

-25°C to +30°C 

3 months 

6 hours

+30°C to +45°C 

2 months 

6 hours

 
15.2.- Batteries Replacement: 

This UPS has been designed to allow easy and safety battery replacement 
 

Step 1: Remove front cover and disconnect internal 
batteries 

Step 2: Take out battery kit from UPS

 
 
 
  
 

 
 
 
 
 
 
 
 

Step 3: Replace old batteries using equivalent 
batteries with same voltage and capacity in AH. 
Follow instructions of 15.3 

Step 4: Reconnect batteries, assembly battery kit 
and install it inside the UPS. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

USER MANUAL

 

Optima Rack 1-3K

 

___________________________________________________________________________________________________________________________________ 

(120217_EN) OPTIMA-RACK 1K-3K

 

  

24

 

 

Step 5: Reconnect battery kit to UPS

Step 6: Close front cover

 
 
 
 
 
 
 
 
 

 
 
 
 
15.3.- Battery Assembly Instructions: 

Battery quantity depends of UPS model. Check specification table to know battery quantity and type for your UPS. 
 

3 Batteries Kit

 

1.- Remove batteries from plastic assembly

2.- Connect new batteries in series as indicated 
below 

 
 
 
 
 
 

3.- Place batteries inside plastic assembly

4.- Close battery assembly

 
 
 
 
 
 
 
 

5.- Using a DVM, check battery assembly DC voltage is closet o 37.5 Vdc (3 x 12.5Vdc each). If measured voltage 
is not correct probably there is a wrong connection. Check, correct and confirm. 

 
 

Summary of Contents for OPTIMA-RACK 1KVA

Page 1: ...care Do not block UPS ventilation WARNING Make sure to connect this unit to proper power line according to selected model The UPS Technical Specs sticker shows power rating information DO NOT connect...

Page 2: ...1 2003 An Uninterruptible Power Systems UPS Part 1 1 General and Safety Requirement for UPS use operator access areas EMC Directives EN62040 2 2006 An Uninterruptible Power Systems UPS Part 2 Electro...

Page 3: ...TON FUNCTIONS ON MUTE a POWER ON Keep selected during 2 seconds or longer b BEEP MUTE In battery mode Keep selected during 5 seconds or longer to Mute acoustic alarm beep Some alarms cannot be muted a...

Page 4: ..._____________________________________________________________________________________________ 120217_EN OPTIMA RACK 1K 3K 8 3 2 RACK UPS INSTALLATION Rack UPS must be installed using L Shape type guid...

Page 5: ...OPTIMA models but they can also be connected at any moment to EX BATT supplied by XMART Special cables to connect EX BATT to UPS are supplied inside the box of EX BATT USER MANUAL Optima Rack 1 3K ___...

Page 6: ...power from batteries There is no dead time transition time is ZERO ms related to switching from normal mode to battery mode since load is always powered from inverter This is main characteristic of a...

Page 7: ...ry charging level 0 25 26 50 51 75 y 76 100 Indicates battery failure Indicates low battery level Input Information Indicates input voltage input frequency and DC battery voltage Vac Input voltage Vdc...

Page 8: ...ts To able or disable programmable outlets function 09 Programmable To configure timer value in minutes for programmable outlets USER MANUAL Optima Rack 1 3K __________________________________________...

Page 9: ...as selected BATTERY MODE When AC input source is out of range Ups goes to battery mode to supply output from taking energy from batteries USER MANUAL Optima Rack 1 3K _________________________________...

Page 10: ...push button is not been selected properly Push ON button during 2 seconds or longer 1 beep s alarm is active and LCD shows Input Line and Neutral are swapped Rotate UPS plug at wall socket to allow c...

Page 11: ...th terms and conditions stipulated herein Transportation expenses are not covered by this limited warranty 3 Warranty is valid only if the original purchasing document issued to original purchaser by...

Page 12: ...ries Step 2 Take out battery kit from UPS Step 3 Replace old batteries using equivalent batteries with same voltage and capacity in AH Follow instructions of 15 3 Step 4 Reconnect batteries assembly b...

Page 13: ...apacidad 1100VA 800W 1700VA 1200W 2250VA 1600W 3400VA 2400W Range Rango Vac 100 load Model 120V 80Vac 150Vac Model 220V 160Vac 300Vac Range Rango Vac 50 load Model 120V 50Vac 150Vac Model 220V 110Vac...

Reviews: