background image

       

Extension ED module                           

                                    XD-4GBOX-ED

 

               

             

Fast manual 

Thanks  for  purchasing  XINJE  XD  series  PLC  and  extension  module.  This  manual  will 
introduce the electric features and using method of XD series extension ED module. Please 
read this manual carefully before using the products, make sure the wiring operation is safe.   

       

Features of analog extension module   

        XD-4GBOX-ED 

 

Remote diagnosis of equipment fault 

 

Equipment after-sales maintenance, such as air compressor 

 

Ensure the test equipment data is real and reliable, such as Li battery test 

 

Intellegent  city  construction,  such  as  sewage  treatment,  waste  recycling,  cold 

storage 

 

Intellegent agriculture and car industries, smart home 

 

Safety precautions                                                                   

 

Control system design attentions 

 

     

Dangerous!

   

 

Make  sure  design  the  safety  circuit,  to  ensure  that  the  control  system  can  still  work 

safety when the external power supply cut off or PLC broken.   

 

Make sure set emergency braking circuit, protection circuit, interlock circuit of forward-

reverse running in PLC external circuit and upper-lower limit switch to prevent from 

machine damage. 

 

In order to make the equipment safe operation, please design external protection circuit 

for important output signal. 

 

PLC CPU will close all the output when detecting the system error; the output will lose 

control when the PLC circuit has problem. Please design suitable external control circuit 

to ensure the device working normally. 

 

If the PLC relay or transistor unit is broken, the output cannot be ON or OFF. 

 

The PLC is designed for indoor environment, the lightning protection must be installed 

in the power supply system to avoid PLC and other device damage. 

 

Installation and wiring attentions 

 

 

   

Dangerous!

   

 

Do  not  use  the  PLC  in  the  following  environment:  dust,  soot,  corrosive  gases, 

flammable gas, high temperature, condensation, vibration, impact, lightning, fire. 

 

Do not let the metal scrap and wire head drop into the ventilation hole of PLC, otherwise 

it will cause fire or error operation. 

 

Do not cover the ventilation hole of PLC, otherwise it will cause fire, error operation. 

 

The I/O wiring must be fixed enough, otherwise the bad contactor will cause fault. 

 

Attention!

   

 

It can use external power supply for extension module DC24V power. 

 

Please use shield cable for high frequency I/O wiring to avoid interference.   

 

Run and maintenance 

       

Dangerous!

   

 

Please connect all the cable include PLC, extension module and BD board after shutting 

down the power supply. 

 

Please operate as the manual for online operation, forced output, RUN, STOP.   

 

Attention!

   

 

Please discard the product as industrial waste. 

 

Make sure cut off the power supply when installing or uninstalling the extension card.   

 

Product information                                                                             

 
 

 

Naming rule 

XD– 4GBOX - ED 

               

②         

 

         

① 

Product series            XD: XD series extension module 

② 

Module name            4G: 4G communication module 

③ 

ED                              left extension 

 

Basic parameters 

XD series PLC can connect 1 extension ED module, the type is not limited. 

 

Table 1: analog extension module XD-4GBOX-ED general specifications 

Item   

Specifications   

Using environment 

No corrosive gas 

Environment temperature 

0

~60

 

Storage temperature 

-20~70

 

Environment humidity 

5~95%RH 

Storage humidity 

5~95%RH 

Installation   

Fix with  M3 screw or install  on the rail DIN46277(width 

35mm) 

 

的导轨上

 

Dimension   

25mm×100mm×90.0mm 

Table 2: analog extension module XD-4GBOX-ED product features 

Parameters   

Description   

Working frequency 

GSM/GPRS: 900, 1800MHz        EDGE: 900, 1800MHz 

UMTS: CDMA2000(BC0), WCDMA(B1, B8),   

TD-SCDMA(1.9G, 2G) 

LTE: FDD(B1, B3, B8)    TDD(B38, B39, B40, B41) 

GNSS: GPS, GLONASS 

Max transmission speed 

100 Mbps 

Max transmitting power 

GSM/GPRS: 2W        EDGE: 0.5W 
UMTS: 0.25W          LTE: 0.25W 

Working temperature 

-10

~50

 

Average standby current 

<5mA 

 

 

Product appearance                                                                                                 

 

Product structure 

         

 

 

 

 

 

Product dimension and installation                                   

 

Product dimension 

  (Unit: mm)

 

XD series extension ED module XD-4GBOX-ED dimension is shown as below:

 

 

 

 

Installation 

Please connect the extention cable of XD-4GBOX-ED to XD series PLC left ED port, and 

install with screw or fix on DIN46277 rail. 

Note: 

(1)

 

Please do not let the chip and wire cuttings fall into the module when installing. 

(2)

 

Please confirm the module and equipment specification before wiring. 

(3)

 

Please pay attention to whether the connection is fixed and the loss of connection will 

cause incorrect data and short circuit. The installation, wiring and other operation must 

be done after the power supply is cut off. 

Electric design reference                                                                   

 

Structure 

 

Terminals 

 

Note: the view direction is facing the module at front side, the terminal sequence from up to 
down is +24V, 0V, FG. The module power supply voltage is 24V DC, the range is DC21.6V 
to 26.4V. 
 

 

Status indicator 

 

Light   

Function   

PWR 

Module power supply 

COM 

Module and PLC serial port connection succeeded 

LINK 

Log on target server succeeded 

NETSTATUS 

Visit telecom operator and build the network 

 

Signal strength 

The  module  running  state,  4GBOX  visiting  server  succeeded.  L0~L3  show  the  signal 

strength of network. In error state, L0~L3 will show the error type, please see below table:   

L0 

L1 

L2 

L3 

Explanation   

flashing 

No SIM card or SIM card insert error 

flashing 

flashing 

4GBOX  cannot  open  the  network  (SIM 
card  arrears  or  not  open  the  data  traffic 
service) 

flashing 

flashing 

flashing 

flashing 

4GBOX not configure server information 

 

DIP switch 

S1 

S2 

S3 

S4 

If the serial port configuration of 4GBOX is error and cannot connect the PLC, please turn 

on  switch  1,  then  repower  on  the  module  to  restore  the  out  of  factory  parameters.  The 

configured serial port connection flag, signal strength flag, SIM binding flag, white list still 

exist, no need to configure again. But remote parameters and serial port parameters are back 

to default value. 

S1 

S2 

S3 

S4 

Function   

ON 

OFF 

Back to default parameters when re-power on 

OFF 

OFF 

Running mode 

ON 

Factory mode (XD-4GBOX-ED) 

ON 

Configuration mode (4GBOX-M) 

 

Initialization time 

The module initialization time is depend on the telecom operator. The table shows the time 

of Chinese telecom operators: 

Telecom operator 

Initialization time (s)

 

China mobile 

21.31 

China unicom 

23.24 

China telecom 

59.89 

 

Using steps                                                                         

 

 

Preparation 

 

Open the function of data traffic for the Nano SIM card   

 

Open the message function (optional) 

 

XD series PLC hardware V3.4.5 and up 

 

XD/EPPro programming software V3.5 and up 

 

XD series PLC programming cable 

 

PC (enable to visit internet, installed XD/EPPro software) 

 

 

Module configuration 

4GBOX  is  the  left  extension  ED  module  of  XD  series  PLC,  the  configuration  needs 

XD/EPPro software and Config tool. Please make sure the PLC hardware version is V3.4.5 

and up, XD/EPPro version is V3.5 and up, XinjeConfig tool version is v1.6.343 and up. 

 

Serial port 

 

XD  series  PLC  serial  port  communication  protocol  includes  Modbus  RTU,  XNET 

(OMMS/TBN/PPFD), free format protocol. For 4GBOX, PLC serial port protocol must set 

to  XNET-PPFD,  physical  layer  is  TTL.  The  baud  rate  must  be  same.  Network  number, 

station number is recommended to use default parameters.   

PWR
COM
LINK

+24V

0V
FG

NETSTATUS

SIM

4G

PWR
COM
WIFI
LINK

+24V

0V
FG

PWR
COM
LINK

+24V

0V
FG

NETSTATUS

SIM

4G