Table A-5
X6000 V6 server heat dissipation and air volume requirements
X6000 V6 Power
Environment and Air Volume Requirement of a
Single-Chassis Server
3000W-4000W
⚫
Air inlet temperature: ≤ 35°C (95°F)
⚫
Air volume supplied in the equipment room for a
single device: ≥ 350 CFM
⚫
Cooling capacity supplied in the equipment room for a
single device: ≥ 4000 W
Lower than 3000 W
⚫
Air inlet temperature: ≤ 35°C (95°F)
⚫
Air volume supplied in the equipment room for a
single device:
−
8080 fans: ≥ 270 CFM
−
8080+ fans: ≥ 300 CFM
⚫
Cooling capacity supplied in the equipment room for a
single device:: ≥ 3000 W