User Manual - DINgate TM
26 October 2021
XEMEX Confidential
Page 11 of 20
4
Installation instructions
4.1
Guidelines for safety and installation
This installation guide must be consulted in all cases when manipulating parts which are marked
with the Caution symbol.
The installation and the operation of this device and any maintenance must be carried out by a
qualified person in accordance with specific local standards and safety regulations.
Caution: never open the secondary circuit of a Current Transformer while current is flowing
through the primary circuit!
If the secondary circuit is opened when primary current is flowing, then the voltage will go to a very
high value, possibly causing electrical arcing and/or electrical shock to service personnel. Therefore
CT’s with internal TVS must be used.
Failing to obey the ”Guidelines for safety and installation”, the guarantee no longer applies.
4.2
Mounting
Mount the device in a DIN rail cabinet.
4.3
Electrical wiring diagram
WARNING
The DINgate TM module power connection always needs to be protected with a circuit
breaker.