background image

LITHIONICS BATTERY, CLEARWATER, FL 33759 USA

PH: 727.726.4204 |    FAX: 727.797.8046 |    WEB: LITHIONICSBATTERY.COM

1. Using the SCP display/interface select your SW3012 

2. Press the Enter, Up and Down arrow together to enter 

Advanced Settings Mode

3. Once 

Advanced Settings Mode

 has been enabled enter the following settings into their respective menus

Inverter Settings

Low Batt Cut Out

12.1V*

LBCO Delay

10Sec

High Batt Cut Out

15.2V

Charger Settings

Batt Type

Custom

Custom Settings

Eqlz Support

Disabled

Bulk Voltage

14.6V

Absorb Voltage

14.6V

Float Voltage

13.4V

Batt Capacity

[Enter Ah of Your System]

Max Charge Rate

100%

Charge Cycle

3 Stage

Default Batt Temp

Warm**

Recharge Volts

12.4V***

Absorb Time

30min****

Auto Charge Enable Enabled

*Use 12.1V for systems which have “RVC” 

Enabled 

in the Lithionics Battery Management System. For systems with “RVC” 

Disabled 

this can be set lower between 11.2V – 12.0V which will allow a lower depth of discharge.

** Do NOT use the Xantrex battery temperature sensor as it is not needed with the Lithionics Battery LiFePO4 battery system.

*** This is the recommended setting but should be adjusted depending on the installation site’s intended usage pattern.

Ex. 1 - Grid-Tie Home/Building UPS would use a higher recharge voltage (ex. 13.3V) to ensure the battery is fully 
charged and ready for when Grid power is lost.
Ex. 2 – Off-Grid Solar System where energy from the battery is stored during the day and then intentionally 
consumed during the night will use a lower recharge voltage setting (ex. 12.0 – 12.4V).

**** 30min setting is the recommended starting point but it may need to be reduced/increased due to varying Ah capacity sizes 
of different Lithionics Battery LiFePO4 battery systems. This can be determined experimentally by monitoring the absorb stage of 
charging cycle. Ideally absorb time should end when charging amperage is at 

1/30

th

 the capacity of the system or less.

Example: System is a 12V 600Ah, absorb time should end when amperage reduces to 600Ah/30 = 20A. So by watching 
the absorb cycle and timing it, when the charging amperage naturally reduces to 20A at this time point in minutes is 
what the absorb time should be set to.

Reviews: