Basic Installation Procedures
975-0767-01-01
45
GFCI Connections
NOTICE
RISK OF EQUIPMENT DAMAGE
Use the 15 A supplementary protector for the GFCI receptacle
only. The breaker is not intended for use in branch circuits.
Failure to follow these instructions can result in equipment
damage.
To install a GFCI on the unit:
1. Ensure AC and DC power sources are turned off, if not
already done from
AC Input Connections on page 40
.
2. Install the required circuit breaker in the inverter distribution
panel receiving AC power from the inverter.
3. Remove the wiring compartment cover, if not already done
from
AC Input Connections on page 40
WARNING
ELECTRIC SHOCK HAZARD
Use a screwdriver to loosen the captive nut panel screw.
Failure to follow these instructions can result in death, serious
injury, or equipment damage
.
4. Prepare the following:
l
one 5" (127mm) black AC wire (for Line connection)
l
one 5" (127mm) white AC wire (for Neutral connection)
l
one 5" (127mm) green AC wire (for Ground connection)
l
three spade ferrules
l
three straight ferrules
l
one twist-on wire connector (marrette)
5. Remove the GFCI cover plate by removing the two screws
holding it in place.