Configuring the Freedom SW using the SCP
Inverter Settings Menu
The
Inverter Settings
menu contains settings that control when
the Freedom SW 230V starts and stops producing AC output.
Figure 28
Inverter Settings Menu Screen
Table 8
Setting Defaults and Ranges
Model
Freedom SW 230V
Item
Default
Min
Max
Low Batt Cut Out
21.0V
20.0V
24.0V
LBCO Delay
10sec
0sec
600sec
Hi Batt Cut Out
33.0V
29.0V
15.5V
Search Watts
50W
5W
250W
Search Delay
2sec
1sec
25sec
FSW3524E 00: Inv Settings
Low Batt Cut Out
LBCO Delay
Hi Batt Cut Out
Search Watts
Search Delay
[22.0]
[10sec]
[31.0V]
[50W]
[2sec]
Table 9
Inverter Settings Description
Item
Description
Low Batt Cut Out
Low Battery Cut Out (LBCO) controls when the inverter stops
producing AC output due to a low battery voltage condition. The
inverter will stop producing AC output only after this level has been
reached for the period of time set by the
LBCO Delay
. This setting is
not temperature compensated.
LBCO Delay
LBCO Delay controls how long the inverter is allowed to operate at or
below the
Low Batt Cut Out
level before turning off due to a low
battery voltage condition. The inverter will stop producing AC output
only after the
Low Batt Cut Out
level has been reached for this
uninterrupted period of time.
Once the inverter has shut off, the battery voltage must rise 4 volts
above the
Low Batt Cut Out
setting for inverter operation to
resume.
Hi Batt Cut Out
Hi Batt Cut Out sets the maximum battery voltage at which the inverter
will operate. If the battery voltage exceeds this limit for more than one
minute, the Freedom SW 230V displays a fault message and shuts
down. The inverter will not support AC loads when in this condition. If
a qualified AC source is present, the unit passes AC through to the
loads. The inverter automatically restarts when the voltage drops to
3 volts below the
Hi Batt Cut Out
setting. If battery voltage
continues to rise after shutdown, an external charger may still be
charging the batteries. The Freedom SW 230V cannot control how
external chargers operate.
Search Watts
Search Watts sets the Freedom SW 230V’s search sensitivity when
search mode is enabled. When a load larger than this setting is present,
the inverter starts producing AC output. Enabling search mode from
the
Setup
menu (see page 57) can minimize power draw from the
battery during periods of low demand from loads. Also see “Using
Search Mode” on page 39.
FSW 230V Owners Guide.book Page 49 Tuesday, August 7, 2018 9:38 AM
Summary of Contents for Freedom SW 230V 815-3524-02
Page 2: ...FSW 230V Owners Guide book Page ii Tuesday August 7 2018 9 38 AM...
Page 10: ...FSW 230V Owners Guide book Page viii Tuesday August 7 2018 9 38 AM...
Page 14: ...FSW 230V Owners Guide book Page iv Tuesday August 7 2018 9 38 AM...
Page 98: ...FSW 230V Owners Guide book Page 84 Tuesday August 7 2018 9 38 AM...
Page 103: ...FSW 230V Owners Guide book Page i Tuesday August 7 2018 9 38 AM...