Adjusting Settings in Configuration Mode
40
Freedom EX 4000 Owner's Guide
AC Sub-settings
Setting Name
Setting
Number
Default
Value
Range of Values
Unit Step
Description
AC Low Voltage
Cutout
A1
80
60
to
115
V
1
Sets the minimum acceptable AC input voltage
level.
AC Low Frequency
Cutout
A2
55
44
to
59
Hz
1
Sets the minimum acceptable AC input
frequency level.
AC High Frequency
Cutout
A3
65
61
to
68
Hz
1
Sets the maximum acceptable AC input
frequency level.
Generator Support
Mode
A4
65E
(enable)
65E
(enable)
65d
(disable)
--
--
Enables or disables Generator support mode.
Generator Support
Current
A5
40
0
to
40
A
1
Sets the generator load level at which the
inverter supplies power from the batteries to
support the generator.