Xantrex C12 Charge/ Load / Lighting Controller Owner’s Manual 

 

975-0130-01-01 

 

 

 

   7 

Testpoints for Voltage Settings

 

If greater accuracy is desired, or if the knobs have been removed, 
testpoints are provided for measurement of each setting. A digital 
voltmeter needs to be connected from the BAT- terminal on the circuit 
board and the small testpoint located to the left of each adjustment pot 
at the 9 o’clock position. The testpoint provides a reading from 0 to 2 
volts—this value must be added to the lower value of the adjustment 
range (HVD=13.0, HVR=12.5, LVR=12.0, LVD=10.5). 
For example, to set the BULK (HVD) voltage to 14.4 volts, adjust the 
pot until the testpoint reads 1.4 volts (13.0 V + 1.4 V = 14.4 V).  

 

C12 circuit board shown at actual size 

Testpoint for NITE LITE TIME 

A testpoint is also provided to assist with the precise adjustment of the 
NITE LITE TIME control. Measurement of the testpoint with a digital 
voltmeter provides a voltage reading that can be used to validate the 
control knob’s setting by comparing with the ranges shown below. 

NITE LITE TIME Adjustment Using the Testpoint 

Testpoint Reading 

Mode or Time Period of Light Operation 

0.50V to 1.40V 

Manual reset of loads required after LVD 

1.45V to 2.65V 

Automatic reset of loads after LVD 

2.70V to 4.90V 
+0.04V = 10 min. 

NITE LITE mode with adjustable time period 
Adjustable in 10 min. periods up to 9.5 hours 

4.92V to 5.00V 

D-D mode (Dusk to Dawn / 20 hours max.) 

Measurement needs to be from testpoint to BAT- terminal on the C12 

 

Typical Installation 

Basic installation of a small photovoltaic system with the C12 is shown 
below. The fuses are needed to protect against short circuits of the 
battery and the wiring to the C12. Disconnects may be required and 
are not shown. The PV array frame, C12 chassis and DC loads should 
be grounded. Check your local electrical code requirements. 

 

PV  - 

PV + 

LOAD  - 

LOAD + 

BAT  - 

BAT + 

PV ARRAY UP TO 15 AMPS 

(SHORT CIRCUIT RATING) 

XANTREX 

C12 

DEEP CYCLE 

12V BATTERY 

FUSE   

FUSE   

12VDC - 120VAC 

INVERTER 

12VDC LOAD 

DISTRIBUTION

DC LOADS 

LIGHTS 

DC LOADS 

RADIO/TV 

POS NEG 

POS 

NEG 

POS 

NEG 

POS 

NEG 

POS 

NEG 

 

Limited Warranty

 

What does this warranty cover? 

This Limited Warranty is provided by Xantrex Technology, Inc. 

("Xantrex") and covers defects in workmanship and materials in your 

Xantrex C12. This warranty period lasts for two (2) years from the date 

of purchase at the point of sale to you, the original end user customer. 

You require proof of purchase to make warranty claims. 

What will Xantrex do?  

Xantrex will, at its option, repair or replace the defective product free of 

charge, provided that you notify Xantrex of the product defect within 

the Warranty Period, and provided that Xantrex through inspection 

establishes the existence of such a defect and that it is covered by this 

Limited Warranty. 
Xantrex will, at its option, use new and/or reconditioned parts in 

performing warranty repair and building replacement products. Xantrex 

reserves the right to use parts or products of original or improved 

design in the repair or replacement. If Xantrex repairs or replaces a 

product, its warranty continues for the remaining portion of the original 

Warranty Period or 90 days from the date of the return shipment to the 

customer, whichever is greater. All replaced products and all parts 

removed from repaired products become the property of Xantrex. 
Xantrex covers both parts and labor necessary to repair the product, 

and return shipment to the customer via a Xantrex-selected non-

expedited surface freight within the contiguous United States and 

Canada. Alaska and Hawaii are excluded. Contact Xantrex Customer 

Service for details on freight policy for return shipments outside of the 

contiguous United States and Canada. 

TESTPOINTS

 

NITE LITE TIME 

TESTPOINT 

Connect a DC to AC inverter 
directly to the battery (instead 
of to the C12 load terminals) 
if it is rated over 150 watts or 
if it has its own low voltage 
disconnect (LVD) protection 
circuitry built in. 

Summary of Contents for C12

Page 1: ...er s Manual t 1 800 670 0707 toll free in North America 1 360 925 5097 direct f 1 800 994 7828 toll free in North America 1 360 925 5143 direct e customerservice xantrex com www xantrex com March 2004...

Page 2: ...e battery minimizing watering requirements and ensuring the complete recharge of the battery Automatic PV Array Night Disconnection Each night the PV array is automatically disconnected from the batte...

Page 3: ...3v per C for lead acid type batteries and 0 02v per C for NiCad type batteries If the temperature sensor is not installed the setpoints should be adjusted to account for the temperature of the battery...

Page 4: ...nnect mode was selected the loads will be turned off momentarily flashed to warn the user that the battery is empty after a 2 minute delay The loads will then be disconnected after an additional 5 min...

Page 5: ...antrex Technology model number C12 charge load controller for use in Residential and Commercial photovoltaic applications The C12 has been certified by ETL to UL specification UL Standard 1741 draft P...

Page 6: ...r pole from directly behind the controller As a minimum a 20 amp DC rated fuse in an appropriate fuse holder or disconnect switch should be provided near the battery for protection from short circuits...

Page 7: ...T PV ARRAY UP TO 15 AMPS SHORT CIRCUIT RATING XANTREX C12 DEEP CYCLE 12V BATTERY FUSE FUSE 12VDC 120VAC INVERTER 12VDC LOAD DISTRIBUTION DC LOADS LIGHTS DC LOADS RADIO TV POS NEG POS NEG POS NEG POS N...

Page 8: ...UCT Exclusions If this product is a consumer product federal law does not allow an exclusion of implied warranties To the extent you are entitled to implied warranties under federal law to the extent...

Reviews: