Place the device with the upper guide edge on 
the top-hat rail. 
Then press the device gently downward until it 
engages with the fastening safety catch on the 
top-hat rail. 

 
When wiring the data lines, please refer to the description of the "FRIGOENTRY bus system". 

We recommend the use of shielded cables for sensor extension. 
 

Cable length 

Cross section 

Up to 100m 

0.75mm² 

Up to 400m 

1.5mm² 

 

 
 

Technical data 

 

Power supply 

230V~, +10% / -15%, approx. 5VA 

Temperature sensor 

TRK277/7 PLUS or DGF 

Pressure sensor 

p

0

: -0.5...7bar (corresponds to 4...20mA) or 0...25bar (corresponds 

to 4...20mA) 
p

c

: 0...25bar (corresponds to 4...20mA) 

Digital inputs 

Inputs for voltage-free contacts: 
1 x setpoint increase (

T

0

2 x peak load shedding (I and II) of which 1 x multifunctional input (II) 
1 x fast return (FR) 

Output relay 

4 x normally open contact, 230V~, 4(2)A, rated voltage 230V~ 

Analogue output 

0...10V=, non-floating, max. load 10mA, for connection of ADC 
(multiple contact switch), speed regulator or frequency converter for 
condensation pressure control 

Central unit 

Single-chip microcomputer, data memory 

Monitoring system 

Monitoring of connected sensors, self-monitoring of data memory 
and microcomputer 

Communication 

3-wire CAN bus interface with integrated power supply, galvanically 
isolated, service socket 

Dimensions  

(WxHxD) 106 x 90 x 58mm (DIN 43880) 

Fastening 

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715) 

Ambient temperature 

Operation: 0...+55°C, storage: -25…+70°C 

Weight  

About 450g 

CE conformity 

  2014/30/EU (EMC Directive) 

  2014/35/EU (Low Voltage Directive) 

 

EAC conformity 

  TR CU 004/2011 

  TR CU 020/2011 

 

 

RoHS II 

Valid from 

Version 1.70 

 

 