PROFIBUS connection
System 182
7 - 6
ba75503e07
04/2012
7.5
Transmitted sensor data
7.5.1
Overview
Course of the data
transmission
The basis for data transmission between the PROFIBUS master and
IQ S
ENSOR
N
ET
is formed by the unique assignment of a sensor to its
sensor number (Sxx) in the IQ S
ENSOR
N
ET
system. The sensor
numbers are assigned by the system in the order in which the sensors
are recognized by the system.
The sensor number (Sxx) is the identification for a sensor. The sensor
number is always transmitted in the first byte of the output and input
data. Thus the PROFIBUS master can clearly query data of individual
sensors.
The data is transmitted in two steps:
The Profibus master transmits the request to the DIQ/S 182-PR to
supply data for the sensor with a certain sensor number.
The DIQ/S 182-PR checks whether the requested sensor number is
present and returns the data for the sensor with the respective
sensor number to the PROFIBUS master.
Fig. 7-3
Course of the data transmission in the PROFIBUS
master
Read input data
Is sensor number identical
in input data and output data?
Is sensor number identical
in input data and output data?
Input data:
Process data for sensor
Input data:
Process data for sensor
Prompt data of a sensor
with a different sensor number?
Prompt data of a sensor
with a different sensor number?
Output data:
Allocate sensor number (Sxx) for a sensor
Output data:
Allocate sensor number (Sxx) for a sensor
no
no
Start
Summary of Contents for DIQ/S 182-PR
Page 6: ...Contents System 182 0 4 ba75503e07 04 2012 ...
Page 10: ...Overview System 182 1 4 ba75503e07 04 2012 ...
Page 14: ...Safety instructions System 182 2 4 ba75503e07 04 2012 ...
Page 78: ...Operation System 182 4 18 ba75503e07 04 2012 ...
Page 84: ...The SETTINGS menu System 182 5 6 ba75503e07 04 2012 ...
Page 110: ...Relay outputs System 182 6 26 ba75503e07 04 2012 ...
Page 122: ...PROFIBUS connection System 182 7 12 ba75503e07 04 2012 ...
Page 124: ...Maintenance and cleaning System 182 8 2 ba75503e07 04 2012 ...
Page 130: ...What to do if System 182 9 6 ba75503e07 04 2012 ...
Page 142: ...Accessories and options System 182 11 2 ba75503e07 04 2012 ...
Page 146: ...Appendix store separately if required System 182 13 2 ba75503e07 04 2012 ...