Relay outputs
System 182
6 - 16
ba75503e07
04/2012
6.4.3
Sensor monitoring
Function
The
Sensor monitoring
function enables to monitor sensor errors and
the maintenance condition.
In order to set up the
Sensor monitoring
function for a relay output, the
relay output must be linked with a sensor (see section 6.2.1).
Settings
Note
Preferably set up the relay output as an opener for monitoring
functions.
Sensor messages include errors and information that are registered by
the sensor.
Special
sensor errors
The special sensor errors are sensor-dependent. Details of this are
given in the component operating manual of the respective sensor.
General
sensor errors
Setting
Selection
Explanation
Errors
All
All sensor errors (special ones
and general ones) are
monitored and can prompt a
relay action.
Special
Special sensor errors are
monitored and can prompt a
relay action.
Off
Sensor errors are not
monitored.
Mainten. condition
On
Off
Switching on and off the
maintenance condition is
monitored and can prompt a
relay action.
Action
Open
For all functions of the
Sensor
monitoring
, the relay action is
set to
Open
.
Init
can prompt a relay action for a short time, depending
on the starting behavior of the system
----
Invalid measured value, or defective sensor
Error
Communication with sensor interrupted
OFL
Measuring range undercut or exceeded (overflow)
Summary of Contents for DIQ/S 182-PR
Page 6: ...Contents System 182 0 4 ba75503e07 04 2012 ...
Page 10: ...Overview System 182 1 4 ba75503e07 04 2012 ...
Page 14: ...Safety instructions System 182 2 4 ba75503e07 04 2012 ...
Page 78: ...Operation System 182 4 18 ba75503e07 04 2012 ...
Page 84: ...The SETTINGS menu System 182 5 6 ba75503e07 04 2012 ...
Page 110: ...Relay outputs System 182 6 26 ba75503e07 04 2012 ...
Page 122: ...PROFIBUS connection System 182 7 12 ba75503e07 04 2012 ...
Page 124: ...Maintenance and cleaning System 182 8 2 ba75503e07 04 2012 ...
Page 130: ...What to do if System 182 9 6 ba75503e07 04 2012 ...
Page 142: ...Accessories and options System 182 11 2 ba75503e07 04 2012 ...
Page 146: ...Appendix store separately if required System 182 13 2 ba75503e07 04 2012 ...