Proportional output
In the case of proportional output, a relay switches cyclically on and off
in a defined measured value range (proportional range). At the same
time, the relay switches with a:
!
duration of operation that corresponds to the measured value
(pulse-width output, see page 4-7) or
!
switching frequency (frequency output, see page 4-8).
Proportional outputs can be used in the following way:
!
Output with one relay:
An output range is defined with a
Start value
and an
End value
. No
output takes place above and below the output range
(see page 4-6).
!
Output with two relays:
An output range is defined for each relay with a
Start value
and an
End value
. One relay outputs in the upper output range and a further
relay in the lower output range (see page 4-6).