Page 8
RPC-40L8A4 Series; Quick Start Guide
Connecting to the Alarm Inputs
The RPC-40L8A4 back panel includes four alarm inputs, designed for connection to door
open alarms or other dry contact alarms. Each + pin supplies positive DC voltage at the
same voltage that is used to power the unit (i.e., ± 48 V DC units p48 V DC, +24
V DC units p24 V DC and +12 V DC units p12 V DC.)
Note that when the RPC-40L8A4 unit is shipped from the factory, the removable alarm
input connectors are enclosed in separate plastic bag, included in the shipping box and
must be installed by the user.
When connecting wires to alarm inputs, make certain each wire is properly seated and
firmly held in place by the retaining screw. As shown in Figure 5, in order to properly
seat the wire the retaining screw must be turned counter-clockwise until the metal "gate"
in the wire hole is open. If the metal gate is closed, the wire will not seat properly. After
inserting the wires, tighten both screws to secure the wires to the connector and snap the
connector in place on the back panel of the RPC unit.
Caution:
Do not over tighten the retaining screws. The recommended
maximum torque is 4.5 lbf-in (72 ozf-in.)
Input Current
Output Current:
+48, +24 or
+12 V DC
+
-
Retaining
Screws
Wire
Holes
Gate Open
Gate Closed
Alarm Wire
14 to 24 Gauge
Strip 0.25 Inch
(6.35 mm)
Figure 5: Connecting to the Alarm Inputs