Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Commissioning
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
47
of
69
4.3
Performing Measurements before Operation
WARNING!
Risk of injury due to high voltage when measuring!
Improper measurements at high voltage can cause injury.
•
Perform measurements only with appropriate measurement
devices.
•
During measurement, all circuit breakers must be switched in
position
OFF
and all fuse inserts must be removed.
•
The product must only be started by persons who have all
skills described in section Target Audience.
NOTICE
Damage to measuring device due to overvoltage!
Measurements with the incorrect measuring range can cause
damages.
•
Use only measuring devices with the correct measuring range.
Procedure:
1.
Measure
the DC voltage from plus to minus connection at the
DC circuit breaker inside the product (Figure 13).
NOTICE: The voltage must be positive, and the measured values must be within the
specified limits (Table 10).
2.
Measure
the AC voltage on the bottom terminals (-X14) (Figure 12):
Phase to Phase
Phase to N
Phase to PE
NOTICE: The measured values must be within the specified limits (Table 10).
3.
Ensure
that the AC voltage have a clockwise rotary field.
4.
Close
doors.
5.
Pull out
the Enable switch.
6.
Switch
the AC circuit breaker in position
ON
. The DC circuit breaker is
operated automatically.
NOTICE: Operation is started after the appropriate checks via the user interface.