Worcester WM 12 Installation And Servicing Instructions Download Page 24

11.3 Reassembling the Appliance

1.

From the outside of the property carefully insert the external

duct into the wall mounting duct with the oil connection block on
the bottom edge of the duct.

2.

The wall thickness determines how far out of the outside wall

the external duct protrudes. Set the external duct position by
using table 6, fig. 4 and 23.

3. 

For a non-standard wall thickness which does not correspond

to table 6, fig. 4 and 23 proceed as follows:

Cabinet depth in the standard 315mm position

(a)  Non-standard wall thickness within the range of 121 to
313mm the overall distance 

(X),

as shown in fig. 25, from the end

of the wall mounting duct inside the property to the end of the
external duct outside the property should be set at 630mm. 

(b)  Non-standard wall thickness within the range of 314 to 460mm
ensure the external duct protrudes from the property by 45mm.

Cabinet depth in the optional 285mm position

(a)  Non-standard wall thickness within the range of 151 to
343mm the overall distance 

(X),

as shown in fig. 25, from the end

of the wall mounting duct inside the property to the end of the
external duct outside the property should be set at 630mm. 

(b)  Non-standard wall thickness within the range of 344 to 460mm
ensure the external duct protrudes from the property by 45mm.

4.

Pack the external duct in the desired position to prevent move-

ment in assembly. Check the external duct is level or slightly
sloping downward towards the outside of the property using a
spirit level.  In the event of an oil leak this will prevent oil entering
the property.

5.

Place the wall trim 'U' section over the top of the external duct

as shown in fig. 3.  Bend the tabs at the top of the 'U' section if
loose to ensure a tight fit. (See fig. 3.)

6.

Insert the N

o

6 screws provided into the remaining section of

wall trim.

7.

Place the bottom section screw side down in behind the 'U'

section, slide the screws into the slots and tighten the screws to
secure in place.

8.

Mount the external cover onto the external duct ensuring that the

tabs fit over the lip of the external duct. Check that the cover fits cor-

rectly. Make any necessary adjustments to the external duct.  Remove
the cover and wall trim being careful not to move the external duct.

NOTE: Ensure a minimum gap of 5mm (see fig.6) between the
external cover and wall trim to allow sufficient air to enter the
appliance for combustion .

9.

To fasten the external duct to the wall mounting duct use the

locating holes in the back of the external duct to drill four 3mm
holes into the wall mounting duct (see fig. 25).  Using the N

o

6 screws

provided,  screw the external duct to the wall mounting duct.  Check
that the external duct when fastened in place is level or sloping
downwards towards the outside of the property, using a spirit level.
In the event of an oil leak this will prevent oil entering the property.

NOTE: It is important the external duct is level or sloping
slightly downwards towards the outside of the property.

10.

Using the sealant provided, completely seal the joint on all

four sides between the wall mounting duct and the external duct
from the inside of the property (see fig. 25).  

NOTE: It is imperative that the joint between the wall mount-
ing duct and the external duct is completely sealed  to pre-
vent oil or combustion gases entering the wall cavity in the
event of a leakage. 

11.

Slide the internal control box back into position, ensuring

the wall mounting duct earth lead is connected back into the
internal control box. Connect the earth lead to the earth spade
connector. The main harness is routed up the left hand side of
the internal control box in the gap between the control box and
the wall mounting duct (see fig. 2). Screw the internal control box
to the wall mounting duct using the two screws provided.

12.

Using the two screws provided fasten the facia to the internal

control box.

13. 

Connect the earth lead to the service switch assembly and

using the two screws provided fasten the service switch to the
external control box on the external duct (see fig. 3).

There are two grommets on the main harness,  slide the ‘D’
shaped grommets along the cable, fit one into the ‘U’ shaped slot
on the rear of the external control box and the other into the ‘U’
shaped slot on the wall mounting duct.  It is imperative that the
‘D’ shaped grommet is pushed fully in position on the wall
mounting duct as failure to do so might cause damage to the
main harness when the heat exchanger is mounted on the appli-
ance.  Ensure that the main harness does not sag by pulling gen-
tly on the cable when in position to take up the slack (see fig. 25).

14.

Take up any slack on the main harness inside the wall

mounting/external duct by gently pulling the main harness at
position shown in fig. 25.

WARNING: It is imperative the main harness inside the wall
mounting/external duct is not sagging. This will prevent the
main harness being trapped behind the insulation box.

15.

Put cloth or cardboard on the inside on the external and wall

mounting duct to protect the surface while installing the heat exchanger.

16.

Check the wall mounting duct seal as shown in fig. 25. It is

important that this seal is in good condition, replace if damaged.

17.

Pick up the heat exchanger and place inside the duct.

18.

Lift from the bottom so that the flow and return tapings clear

the top of the duct.  Push onto the two studs at the top of the
wall-mounting duct so they protrude through the two holes in
the heat exchanger.  Screw a  M6 nut and washer onto each of
the top two studs, do not tighten.

19.

Push the bottom of the heat exchanger onto the two bottom

studs and screw the remaining two M6 nuts and washers onto
the bottom studs.  Tighten the four nuts to secure the heat
exchanger to the wall mounting duct.

20.

Replace the thermostat phials in their original positions tak-

ing care not to kink the capillaries. They must be positioned so
the application or removal of the cabinet won't damage the capillaries.

21. 

Position the boiler drain tube which is connected to the drain

valve down the back of the internal control box.

Distance External Duct Protrudes

24

Table 6. With the external cover removed the minimum
distance the external duct protrudes from the external
wall for standard wall thickness.

Wall Thickness

(mm)
102*

229
296
460

(inches)

4*

9

12
18

Standard 315mm Position

Optional 285mm Position

140
120

60
45

N/A

150

90
45

* Using the Stand-off kit for a 4 inch wall.

Fig. 23. Distance the external duct protrudes

the external wall.

OUT SIDE
PROPERTY

External duct
(without external cover)

W

A

L

L

See Note

NOTE:

For the distance the external

duct protrudes through the external
wall see table 6 for standard wall
thickness or Section 11.3.3 for non-
standard wall thickness

External cover

Summary of Contents for WM 12

Page 1: ...FIRED PRESSURE JET APPLIANCE INSTALLATION AND SERVICING INSTRUCTIONS BOILER OUTPUT Hot Water and Central Heating MINIMUM 12 kW 41 000 Btu h MAXIMUM 19 kW 65 000 Btu h THESE INSTRUCTIONS APPLY TO UK M...

Page 2: ...all with wall thickness ranging from 102 mm 4 inches to 460 mm 18 inches When installing the appliance on a 102mm 4inch wall the 4inch Standoff Kit must be used The stand off kit reduces the distance...

Page 3: ...5 1 76 2 23 230 11 5 9 21 1 72 000 19 65 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 12 19 Table 2 Electro Oil Inter B9C Burner See Fig 28 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate...

Page 4: ...at Phial retaining spring Frost thermostat 4 Remote lockout reset button Internal control box Thermostat Knob Wall mounting duct Optional programmer position Cabinet 1 7 5 2 4 3 6 1 Wall mounting brac...

Page 5: ...m locking screw Burner hanging bracket Burner mounting flange Burner O shaped gasket Burner Burner Electrical plug lead Burner retaining screw Flue splash plate seal Telescopic flue Flue gasket Telesc...

Page 6: ...n 130mm 70mm 55mm 315mm 315mm 315mm 102mm 4 inch wall with stand off kit 229mm 9 inch wall 296mm 12 inch wall 460mm 18 inch wall NOTE For cabinets set at the optional 285mm position excluding 102 and...

Page 7: ...the split pin from the thermostat phial pocket located in the front right hand side of the boiler Carefully withdraw the control and automatic high limit thermostats from the pocket noting their posit...

Page 8: ...gut ter or painted eaves then an aluminium or stainless steel shield at least 750mm long should be fitted to protect the surface 5 If a terminal is fitted less than 2 metres above a surface to which...

Page 9: ...al facing the terminal 1200 K Vertically from a terminal on the same wall 1500 L Horizontally from a terminal on the same wall 750 NOTE Flue outlet is shown in fig 6 and7 9 L F F K G A E B C D H J NOT...

Page 10: ...il tank is positioned below the burner An inlet and return loop should be created between the de aerator and oil pump De aerators should be fitted externally to the appliance 8 8 The oil supply pipe d...

Page 11: ...5 Double pipe sub gravity feed system MAXIMUM ALLOWABLE PIPE RUN HEAD metres metres 8 mm inside dia pipe 10 mm inside dia pipe 10 mm O D copper 12 mm O D copper 0 35 100 0 5 30 100 1 0 25 100 1 5 20 8...

Page 12: ...Expansion System The feed and expansion pipes must rise continuously from the appliance and must be of the minimum diameter shown in fig 12 The cistern must be arranged to provide a minimum static he...

Page 13: ...t Domestic hot water cylinder Pressure gauge Safety valve To system filling device see fig 14 Fig 14 System filling and make up Heating return Non return valve Non return valve Test cock Temporary hos...

Page 14: ...tor circuits The domestic hot water and radiator circuits are independently controlled by two motorised valves via a cylinder thermostat and a room thermostat Both thermostats switch the water cir cul...

Page 15: ...w green yellow brown brown brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 green yellow brown orange brown brown green yellow blue white grey Time clock white connector brown orange violet 7 8 9...

Page 16: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Page 17: ...rmostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 brown E N N 1 10 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No 42002116 001 Wall mounting duct Control box earth rivet...

Page 18: ...E E N 1 1 2 3 4 5 6 7 8 9 10 C 1 Boiler frost thermostat Lockout reset switch brown 1 2 3 4 5 6 1 2 3 orange E N 1 N 6 4 10 7 E JUNCTION BOX SEE FIG 19 HONEYWELL 10 WAY JUNCTION BOX HONEYWELL PART No...

Page 19: ...mount ed programmer do not wire in this time con troller Wire as shown in Fig 18 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 2 C white V4073A Mid position zone valve 1 N...

Page 20: ...thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of the fa...

Page 21: ...reset thermostat brown blue green yellow E N L L N E E N 1 1 2 3 4 5 6 Time clock white connector 7 8 9 10 Control thermostat Power on indicator Lock out indicator C 1 Drawn viewed from the front of t...

Page 22: ...time con troller Wire as shown in Fig 21 T6160B Room stat green yellow blue 2 1 3 L641A Cylinder stat orange grey 1 C V4043H Hot water zone valve 1 N E 4 5 6 7 8 9 10 L N HTG HW Optional frost thermo...

Page 23: ...l box and wall mounting duct See fig 25 13 Remove the internal control box by undoing the two screws holding the facia to the internal control box and pivot the facia down 14 There is an earth loom th...

Page 24: ...to pre vent oil or combustion gases entering the wall cavity in the event of a leakage 11 Slide the internal control box back into position ensuring the wall mounting duct earth lead is connected back...

Page 25: ...n the wall mounting duct to the external duct 2 No 6 locking screws 3 Completely seal the joint on all four sides between the wall mounting duct and the external duct with the sealant provided 4 Exter...

Page 26: ...en the main oil supply valve at the tank and check for any leaks 4 Remove the flexible oil line from the inlet of the oil pump and place in a suitable container Open the isolating valve between the oi...

Page 27: ...equence is theninitiated Repeattheprocedureuntilaflameisestablished Note Persistent lockout when running indicates a fault and a Service Engineer should be consulted 12 12 Run the boiler for approxima...

Page 28: ...alve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Reassemble in reverse order 7 It is strongly recommended th...

Page 29: ...the inlet to the oil pump goes to the inlet on the connection block and the flexible oil line on the return of the oil pump goes to the return on the connection block 2 With the sponge O shaped gasket...

Page 30: ...cal shut off valve Fig 29 Service switch positions Service Off Run Note Always set the switch to run after servicing Fig 30 Hanging of burner during commissioning service Fire valve clips Burner hangi...

Page 31: ...nsformer Danfoss EBI 052F0030 excludes cable 1 8 716 156 696 0 Mechanical shut off valve 1 8 716 156 658 0 Flexible oil line kit Worcester 1 8 716 157 033 0 Main harness service switch assembly Worces...

Page 32: ...ats Programmer open circuit Check by linking 7 and 9 on the connector Faulty control box Replace if necessary Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 8 716 114 741a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Wo...

Page 37: ...37...

Reviews: