Rectifying faults
23
C1
flashing.
Fan speed too low
Check
Action
1.
Fan lead connector properly con-
nected?
yes:
↓
no:
B
Power OFF the appliance.
B
Plug in connector.
B
Turn ON the appliance.
C6?
2.
Fan lead defective?
yes:
B
Power OFF the appliance.
B
Replace fan lead.
B
Turn ON the appliance.
C6?
no:
↓
3.
Fan defective?
yes:
B
Power OFF the appliance.
B
Plug the connection wire.
B
Replace fan.
B
Plug the connection wire.
B
Turn ON the appliance.
C6?
no:
↓
4.
The PCB control board is damaged.
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Change PCB control board.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.