MAINTENANCE
6 720 648 726 (2011/07)
68
13.2.7 CLEANING THE HEAT EXCHANGER
B
Check the bottom and top sides of the heat exchanger
for dirt.
B
Clean the heat exchanger with compressed air or a
soft brush.
Fig. 118 Cleaning the heat exchanger
B
Refit the condensate collector.
B
Connect the flexible condensate drain hose to the
condensate collector.
B
Re-install the condensate trap.
B
Rinse the heat exchanger with clean water.
B
Reassemble all boiler components in reverse order:
–
Burner with burner seal
–
Burner cover with fan and gas valve
–
Gas valve
–
Glow ignitor and ionisation electrode.
B
Start up the boiler (
Æ
page 47).
13.3 CHECKING AND ADJUSTING THE
GAS/AIR-RATIO
See section 10.2.7 "Checking and adjusting the gas/air-
ratio", page 52.
13.4 FUNCTION CHECK IN OPERATING
CONDITIONS
B
Slowly open the gas valve by pushing on the gas valve
and turning it ¼ rotation in an anticlockwise direction
(
Æ
fig. 79, page 49).
B
Switch on the heating system by pressing the mains
switch of the BC10 basic controller [1].
B
Set the maximum CH flow temperature dial [8] and
the DHW temperature dial [10] to the maximum
temperatures.
B
Enter a heat demand via the control unit and check
that the boiler starts the heating mode.
B
Open a hot water tap and check that the boiler starts
the DHW mode.
B
Set the maximum CH flow temperature dial [8] and
the DHW temperature dial [10] to the required
temperatures.
Fig. 119 BC10 basic controller
CAUTION:
Damage to the installation.
B
Do not use metal brushes or similar hard
cleaning tools.
CAUTION:
Damage to the installation due to
faulty glow ignitor.
The glow ignitor is made from fragile
ceramic material.
B
Do not damage the glow ignitor.
CAUTION:
Damage to the installation due to
dirt particles.
B
Cover up the boiler interior, e. g. using a
blanket or a cover.
CAUTION:
Damage to the installation due to
undesired flue gas or condensate leakage.
B
When installing the condensate collector,
make sure that the two snap closures
close smoothly. If this is not the case, the
seal between the condensate collector
and the flue pipe at the back of the heat
exchanger may be leak.
6 720 648 726-118.1TD
888
1
10
9
8
7
6
5
4
3
2
1
6 720 648 726-069.1TD
11