INSTALLATION
6 720 648 726 (2011/07)
26
8.3
FLUE INSTALLATION
8.3.1
SITING THE FLUE TERMINAL
Fig. 26 Balanced flue terminal position
Terminal position
Minimum spacing:
A
Directly below, above or alongside an opening window, air vent or other ventilation opening
300 mm
B
Below guttering, drain pipes or soil pipes
200 mm
C
Below eaves
200 mm
D
Below balconies or a car port roof Not recommended!
200 mm
E
From vertical drain pipes or soil pipes
150 mm
F
From internal or external corners
300 mm
G
Above adjacent ground, roof or balcony level
300 mm
H
From a surface facing the terminal
600 mm
I
From a terminal facing a terminal
1200 mm
J
From an opening in a car port (e.g. door or window) into dwelling. Not recommended!
1200 mm
K
Vertically from a terminal on the same wall
1500 mm
L
Horizontally from a terminal on the wall
300 mm
M
Adjacent to opening
300 mm
N
Above intersection with roof
300 mm
O
From a vertical structure on the roof
500 mm
The flue for installations in excess of 70 kW must be
installed in accordance with the recommendations of
IGE UP10.
Pluming will occur at the terminal so terminal positions
where this could cause a nuisance should be avoided.
The air supply and the flue gas exhaust must meet the
applicable general regulations. Please consult the
instructions provided with the flue terminal kits prior to
installation.
The boiler MUST be installed so that the terminal is
exposed to external air.
It is important that the position of the terminal allows
the free passage of air at all times.
Minimum acceptable spacing from the terminal to
obstructions and ventilation openings are specified in
fig. 26.
A
F
M
G
M
B,C
F
F
B,C
K
G
K
K
G
C
L
L
A
N
N
O
E
F
J
K
G
D
H, I
6 720 648 726-026.1TD