RECTIFYING FAULTS
8 716 115 748 (2009/09)
31
A6
and fault indicator LED are flashing. Appliance NOT available for demands.
External under floor heating thermostat defective.
Check
Action
1.
B
Power OFF the appliance.
B
Disconnect the appliance electrical
connection.
Check if the external under floor
heating thermostat is connected on
ST8/8-9?
yes:
go to 2
no:
B
Ensure that the link is securely connected to ST8/8-9
B
Reconnect the appliance electrical connection.
B
Power ON the appliance.
A6? go to 4
2.
B
Disconnect lead to thermostat.
Check the thermostat for continuity?
yes:
B
Reconnect lead to thermostat.
go to 3
no:
B
Change thermostat.
B
Reconnect the lead to thermostat.
B
Reconnect the appliance electrical connection.
B
Turn the appliance ON.
A6? go to 4
3
B
Unplug the harness connector that
connects the thermostat to the
control board.
Check the harness for continuity?
yes
A6? go to 4
no
B
Change or repair wiring to the thermostat.
B
Reconnect the appliance electrical connection.
B
Power ON the appliance.
A6? go to 4
4
The control board is damaged.
B
Reconnect the appliance electrical connection.
B
Power ON the appliance.
B
Make a note of the altered service function settings.
B
Power OFF the appliance.
B
Disconnect the appliance electrical connections.
B
Change the control board.
B
Reconnect the appliance electrical connection.
B
Turn the appliance ON.
B
Restore the service settings previously noted.
Tab. 15 A6 Error codes