Manual 35132
VariStroke-DX Duplex Hydraulic Servo Skid
Woodward
30
2. Open VariStroke Cover (using Wrench: Type: Open End; Size: 2 1/4 in, CCW direction )
3. Connect Communication Cable to VariStroke communication port.
To perform VS unit calibration please follow procedure steps according to Woodward manual 35148
(VS-GI Customer Service Tool User Manual).
Once calibration is complete, several transfers should be completed between both VS-I’s with a common
demand signal of 12 mA to ensure that the output of both VS-I’s responds correctly to a switching
demand but also damps quickly and is stable after transfer.
To aid with calibration, pressure gages are provided on the skid assembly (see Figure 3-9). These gages
indicate which unit is in control.