SYNCONpanel - Transportable Remote Synchronizing Panel
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Connector
Connector
Remote
operation
Close
manually
CAN
Bus
I
V
V
GCP-31 RPQ-SC08
V / kV
A (L1)
A (L2)
A (L3)
Operating and Alarm Messages
AUTO
MAN
TEST
STOP
RESET
Setpoint
ON
Mains Parallel
Automatic
Manual
Protection
Alarm
V1
V2
V3
Stop
Genset Control Package
GCP-30
ON
OFF
STOP
Figure 1-2: Typical application of a mobile system
Mobile systems are defined as a generator set with a generator circuit breaker (GCB), which can easily be in-
stalled near a feeder or transformer, and operate as follows:
•
In parallel with mains operation to support the utility [peak load operation]
•
In automatic mains failure mode to operate in case of a mains failure [emergency operation]
•
Independent operation from the utility [isolated operation]
•
With a behavior which allows to open and close the interchange point to the utility [transfer operation]
The GCP-31/
RPQ
+
SC08
supports these modes, which are required for a mobile system.
For maintenance on a interchange point to mains (high voltage transformer or wiring replacement), the GCP-
31/
RPQ
+
SC08
requires the connection to the SYNCON Panel which helps the operator to overtake load from
mains to the mobile system and back. Therefore one or several mobile container(s) can be used.
The GCP-31/
RPQ
+
SC08
offers a special discrete input for the transfer operation and emergency operation. Ad-
ditionally, it offers a special discrete input for connecting an phase rotation relay, which is required for the bus-
bar connection. The other modes are realized through special handling of the given control inputs.